Test Run
3
Initializing Parameters
Initialize the parameters using the following procedure.
To initialize the parameters, set n01 to 8.
Key sequence
Indicator
In approximately
1 s.
4
Setting the Motor Current Parameter
Set the motor current parameter in n32 in order to prevent the motor from burning due
to overloading.
Setting the Rated Motor Current
Check the rated current on the motor nameplate and set the motor current parameter.
This parameter is used for the electronic thermal function for motor overload detection
(OL1). By setting the correct parameter, the overloaded motor will be protected from
burning.
Rated Motor Current
n32
Setting
0.0% to 120% (A) of rated
range
output current of the Inverter
Note 1. The standard rated current of the maximum applicable motor is the default
rated motor current.
Note 2. Motor overload detection (OL1) is disabled by setting the parameter to 0.0.
Display
example
Power On
Press the Mode Key repeatedly until the
PRGM indicator is lit.
Press the Enter Key. The data of n01 will be
displayed.
Use the Increment or Decrement Key to set
n01 to 8. The display will flash.
Press the Enter Key so that the set value will
be entered and the data display will be lit.
The parameter number will be displayed.
Unit of
0.1 A
setting
Chapter 4
Explanation
Changes during
operation
Default setting
No
(see
note 1)
4-7