List of Parameters
Pa-
Name
rame-
ter
No.
n62
UP/DOWN
command
frequency
memory
n63
Torque
compensation
gain
n64
Motor rated slip
n65
Motor no-load
current
n66
Slip
compensation
gain
n67
Slip
compensation
time constant
n68
OMRON's control
reference use
n69
OMRON's control
reference use
n70
OMRON's control
reference use
n71
OMRON's control
reference use
n72
OMRON's control
reference use
n73
OMRON's control
reference use
n74
OMRON's control
reference use
n75
Low-speed
carrier frequency
reduction
selection
n76
OMRON's control
reference use
n77
OMRON's control
reference use
Description
Used to store the adjusted frequency
reference with the UP/DOWN function.
0: Frequency not stored
1: Frequency stored
The frequency must be on hold for 5 s
or more.
Used to set the gain of the torque
compensation function.
The default setting does not need any
changes in normal operation.
Used to set the rated slip value of the
motor in use.
Note Used as the constant of the slip com-
pensation function.
Used to set the no-load current of the
motor in use based on the rated motor
current as 100%.
Note Used as the constant of the slip com-
pensation function.
Used to set the gain of the slip
compensation function.
Note The slip compensation function is
disabled with n66 set to 0.0.
Used for the response speed of the slip
compensation function.
Note The default setting does not need
any changes in normal operation.
Do not change the set value.
Do not change the set value.
Do not change the set value.
Do not change the set value.
Do not change the set value.
Do not change the set value.
Do not change the set value.
Used to select a function to reduce the
carrier frequency when Inverter is at low
speed.
0: Function disabled
1: Function enabled
Note Normally set n75 to 0.
Do not change the set value
Do not change the set value
Chapter 9
Set-
Unit
Default
Changes
setting
ting
of set-
range
ting
0, 1
1
0
No
0.0 to
0.1
1.0
Yes
2.5
0.0 to
0.1 Hz
Varies
Yes
20.0
with
the ca-
pacity.
0 to 99 1%
Varies
No
with
the ca-
pacity.
0.0 to
0.1
0.0
Yes
2.5
0.0 to
0.1 s
2.0
No
25.5
---
---
0
---
---
---
0
---
---
---
0
---
---
---
2
---
---
---
0
---
---
---
10
---
---
---
0
---
0.1
1
0
No
---
---
rdy
---
---
---
0
---
Refer-
during
ence
opera-
page
tion
6-21
6-11
6-12
6-12
6-13
6-13
---
---
---
---
---
---
---
6-4
---
---
9-11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents