Chapter 3 Start Up VFD-B Series

3.2 Operation Method

Refer to 4.2 How to operate the digital keypad VFD-PU01 and chapter 5 parameters for setting. Please
choose a suitable method depending on application and operation rule. The operation is usually used as
shown in the following table.
Operation Method
PU01 keypad
Operate from external
signal

3.3 Trial Run

After finishing checking the items in "3.1 preparation before start-up", you can perform a trial run. The factory
setting of operation source is from keypad (Pr.02-01=00).
1. After applying power, verify that LED "F" is on and the display shows 60.00Hz.
2. Setting frequency to about 5Hz by using
RUN
3. Pressing
should press
STOP
RESET
key.
4. Check following items:
Check if the motor direction of rotation is correct.
Check if the motor runs steadily without abnormal noise and vibration.
Check if acceleration and deceleration are smooth.
If the results of trial run are normal, please start formal run.
3-2
Frequency Source
AVI, ACI, AUI
key for forward running. And if you want to change to reverse running, you
F
H
key in
page. And if you want to decelerate to stop, please press
U
MI1
Parameter
setting:
MI2
04-04=11
04-05=12
DCM
key.
Operation Command
Source
STOP
RUN
RESET
External terminals input:
FWD-DCM
REV-DCM
Revision 10/2005, BE13, SW V4.08