Deviation Range Of Pid Feedback Signal Error; Pg Pulse Range; Pg Input - Delta VFD-B Series Manual

Hide thumbs Also See for VFD-B Series:
Table of Contents

Advertisement

AC motor drive action when the feedback signals (analog PID feedback or PG (encoder) feedback) are
abnormal acc. to Pr.10-16.
10 - 16

Deviation Range of PID Feedback Signal Error

Settings
The base is Pr.01-00. When in PID feedback control, if | Source of PID reference target – feedback | > Pr.10-
16 and exceeds Pr.10-08 detection time, the AC drive will operate according to Pr.10-09.
10 - 10

PG Pulse Range

Settings
A Pulse Generator (PG) or encoder is used as a sensor that provides a feedback signal of the motor speed.
This parameter defines the number of pulses for each cycle of the PG control.
For PG or encoder feedback an option PG-card is needed.

PG Input

10 - 11
Settings
The relationship between the motor rotation and PG input is illustrated below:
FWD
REV
PULSE
GENERATOR
Revision 10/2005, BE13, SW V4.08
0.00~100.00%
1 ~ 40000 (Max=20000 for 2-pole motor)
00
Disable PG
01
Single phase
02
Forward / Counterclockwise rotation
03
Reverse / Clockwise rotation
PG
Chapter 5 Parameters VFD-B Series
A phase leads B phase
A phase
CCW
B phase
10-11=02
B phase leads A phase
A phase
CW
B phase
10-11=03
A phase
CW
B phase
Unit: 0.01
Factory Setting: 100.00
Unit: 1
Factory Setting: 600
Factory Setting: 00
5-109

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents