Chapter 5 Parameters VFD-B Series
01 - 08
Output Frequency Lower Limit
Settings
The Upper/Lower Limits are to prevent operation errors and machine damage.
If the Output Frequency Upper Limit is 50Hz and the Maximum Output Frequency is 60Hz, the Output
Frequency will be limited to 50Hz.
If the Output Frequency Lower Limit is 10Hz, and the Minimum Output Frequency (Pr.01-05) is set to 1.0Hz,
then any Command Frequency between 1.0-10Hz will generate a 10Hz output from the drive.
This parameter must be equal to or less than the Output Frequency Upper Limit (Pr.01-07).
The Output Frequency Lower Limit value = (Pr.01-00 * Pr.01-08) /100.
01 - 09
Acceleration Time 1 (Taccel 1)
01 - 10
Deceleration Time 1 (Tdecel 1)
01 - 11
Acceleration Time 2 (Taccel 2)
01 - 12
Deceleration Time 2 (Tdecel 2)
01 - 18
Acceleration Time 3 (Taccel 3)
01 - 19
Deceleration Time 3 (Tdecel 3)
01 - 20
Acceleration Time 4 (Taccel 4)
5-32
1-08
Output Frequency
Voltage
Lower Limit
1-02
Maximum
Output
Voltage
1-04
Mid-point
Voltage
1-06
Minimum
1-05
Output
Mid-point
Minimum
Voltage
Freq.
Output
Freq.
0 to 100%
1-07
Output Frequency
Upper Limit
The limit of
Output
Frequency
1-03
1-01
Maximum Voltage
Frequency
(Base Frequency)
V/f Curve
Frequency
1-00
Maximum
Output
Frequency
Factory Setting: 0
Revision 10/2005, BE13, SW V4.08
Unit: 1
Unit: 0.1/0.01
Unit: 0.1/0.01
Unit: 0.1/0.01
Unit: 0.1/0.01
Unit: 0.1/0.01
Unit: 0.1/0.01
Unit: 0.1/0.01