NETWORK READ/WRITE Instructions
78
Bit 15 of C+1 determines whether the instruction is for a SYSMAC NET Link
System or a SYSMAC LINK System.
Word
C
Number of words (0 to 256 in 4-digit hexadecimal, i.e., 0000
0100
)
hex
C+1
Response time limit (0.1 and 25.4
seconds in 2-digit hexadecimal
without decimal point, i.e., 00
FF
)
hex
Note: The response time will be 2
seconds if the limit is set to 0
There will be no time limit if the
time limit is set to FF
C+2
Source node number
(1 to 62 in 2-digit hexadecimal,
i.e., 01
hex
Note
1. The node number of the PC executing RECV(98) cannot be set.
2. Set the source node unit number to 00 when sending data to a PC. Settings
01 to 04 specify computer applications 1 to 4.
3. Indirectly Addressed Beginning Destination Flag:
The CV-series PC has a larger data area than the C-series PC. Therefore,
the beginning destination word of the destination node cannot be always
designated by the operand of the RECV instruction. If the beginning destina-
tion word cannot be designated, set the indirectly addressed beginning des-
tination flag to 1 (ON: indirect addressing), in which case the first operand
(S) will be the indirect beginning destination word, and it will be possible to
designate the beginning destination word (rightmost word) of the destina-
tion node in BCD with the word designated by the first operand (S).
Bit
15 14 13 12
Data area code
S + 0
S + 1
Word no. (fourth digit)
This operation is possible with a C200HW-SLK13/14/23/24 SYSMAC LINK
Unit mounted in a C200HX, C200HG, C200HE, C200HS, or C200H PC
only.
Refer to the following table to designate the data area.
Destination node (C-series PC)
Area
I/O (IR)
Link Relay (LR)
Holding Relay (HR)
Auxiliary Relay (AR)
Timer/Counter (T/C)
Data Memory (DM)
Bits 00 to 07
Bits 08 to 11:
to
hex
Bit 12: Indirectly addressed
.
hex
.
hex
Bit 13: Set to 0.
Bit 14 ON: Operating level 0
Bit 15: Set to 1.
Bits 08 to 11:
1
to 3E
)
hex
Bits 13 to 15: Set to 0.
11
10
9
8
7
0
0
Word no. (second
Word no. (third digit)
Destination node (CV-series PC)
Data area
code
00
Core I/O (CIO)
06
CPU Bus Link (G)
07
Auxiliary (A)
08
Timer (T)
03
Counter (C)
05
Data Memory (D)
Extended
Data
Data
Memory (E)
Section 6-2
Bits 08 to 15
to
hex
No. of retries (0 to 15 in
hexadecimal,
i.e., 0
to F
)
hex
hex
beginning destination flag
ON: Indirect addressing
OFF: No indirect addressing
OFF: Operating level 1
(SYSMAC LINK flag)
Source node unit
2
number (0 to 4)
6
5
4
3
2
1
0
0
0
Word no. (fifth digit)
Word no. (first digit)
digit)
Area
Data area
00
01
02
03
04
05
Banks 0 to 7
10 to 17
Current bank 18
code