Power Supply Unit Connection
Wiring
C200H/C200HS
Mounting Position
In the following diagram, a Power Supply Unit is connected to just one SYS-
MAC LINK Unit.
APS SLK
The Power Supply Unit and SYSMAC LINK Unit are connected by a power sup-
ply cable, as shown below. The cable can be plugged into either power supply
connector on the Power Supply Unit.
Power Supply Unit or
SYSMAC LINK Unit
power supply connector
Note
1. Turn off the power supply to the PC before mounting the Power Supply Unit.
2. Firmly tighten the Backplane mounting screws for the Power Supply Unit.
3. Leave the protective sticker in place on the Unit when wiring to prevent clip-
pings and other foreign matter from entering the Unit during the wiring pro-
cedure.
4. Remove the protective sticker after completion of wiring before turning on
power to the Unit. If Unit is operated with the protective sticker in place, the
Unit may overheat, causing operational errors.
5. Do not pull on the cable. Pulling on the cable could break wires inside.
6. Do not bend the cable past the minimum radius. Bending the cable too far
could break wires inside.
The C200H-APS03 can be mounted in any slot, but the power cable included
with the Unit will only reach to the next slot, so the Power Supply Unit must be
mounted next to the SYSMAC LINK Unit.
In the following diagram, a Power Supply Unit is connected to just one SYS-
MAC LINK Unit.
APS SLK
CPU
CPU PS
Section 3-2
Power cable
The tab should be on the left.
23