Omron SYSMAC LINK C1000H-SLK21-V1 System Manual page 43

Table of Contents

Advertisement

Cable Connection
Optical Connector Assembly
Connection Procedure
C1000H-SLK11
1, 2, 3...
5. Master Fiber:
Master Fiber
S3200-CAT2001H
Discontinued Products:
Name
Optical
p
C
Connector
Follow the instructions provided with the S3200-CAK1062 Optical Connector
Assembly Tool Set.
The connection procedure is described briefly below. Begin with the highest
node in the network and connect the lower nodes in order.
Note
1. Turn off the power supply to the PC before connecting the cables.
2. Leave the protective sticker in place on the Unit when wiring to prevent clip-
pings and other foreign matter from entering the Unit during the wiring pro-
cedure.
3. Remove the protective sticker after completion of wiring before turning on
power to the Unit. If Unit is operated with the protective sticker in place, the
Unit may overheat, causing operational errors.
4. Do not pull on the cable. Pulling on the cable could break fibers inside.
5. Do not bend the cable past the minimum radius. Bending the cable too far
could break fibers inside.
6. Do not place heavy objects on the cable or connectors. Heavy objects could
break fibers inside.
1. Insert the terminals into the mounting bracket so that the tension wire holes
are vertical, and then secure the terminals by tightening the nuts on the
other side.
2. Insert the bushings into the mounting bracket and secure the bracket to the
Unit with the Philips head screws provided.
3. If the cable has tension wires, thread them through the terminals and tighten
the terminal screws to secure them.
4. Place the cables behind the clamp and secure them by tightening the Philips
head screw provided. Secure both cables at once.
Applicable Connectors
S3200-COCF2071 (C1000H)
S3200-COCF2571 (C200HS)
Model number
Recommended
replacement
models
S3200-COCF2011 S3200-COCF2071 OMRON
S3200-COCF2511 S3200-COCF2571 OMRON
Section 3-4