Siemens SIMATIC Ident Function Manual page 78

Rfid systems. ident profile, add-on instruction for rockwell systems
Hide thumbs Also See for SIMATIC Ident:
Table of Contents

Advertisement

Configuring the instructions
4.6 Programming the Ident profile
Table 4- 61
Parameter
CMD
EDIT_BLACKLIST_MODE
EPCID_UID
LEN_ID
If "EDIT_BLACKLIST_MODE" = 0x00 or 0x02 was selected, the EPC-ID including the ID length
1)
must be specified.
Table 4- 62
Parameter
CMD
OFFSETBUFFER
RXREF
Table 4- 63
Name
NUM IDS
TAG_DATA
TAG_DATA[1]
TAG_DATA[2]
...
TAG_DATA[n]
78
EDIT-BLACKLIST (only with RF68xR)
GET-BLACKLIST (only with RF68xR)
Result of GET-BLACKLIST
Type
INT
IID_IN_I_80[n
]
IID_IN_I_80
Reserved
SINT
ID_Len
SINT
EPC_ID
SINT[62]
IID_IN_I_80
...
IID_IN_I_80
Value / description
0x7A
0x00 ≙ add EPC-ID
0x01 ≙ Add all "Observed" transponders
0x02 ≙ Delete EPC-ID
0x03 ≙ delete all
EPC-ID
0x00 ≙ unspecified single tag access
Length of the EPC-ID (2-62 bytes)
0x00 ≙ unspecified single tag access
Value / description
0x6C
Offset in the "RXREF" receive buffer
Read black list IDs
Comment
Number of MDS
Length of EPC ID
EPC-ID
Ident profile, Add-on instruction for Rockwell systems
Function Manual, 01/2019, C79000-G8976-C410-03