Error messages
5.2 Errors from the communications module/reader
Error mes-
Description
sage
(hex)
0xE2FE88
General radio protocol error
0xE4FE01
Short circuit or overload of the 24 V outputs
The reader is using too much current.
The reader cable is causing a short-circuit.
Possible consequences:
The affected output is turned off
All outputs are turned off when total overload occurs
A reset can only be performed by turning the 24 V voltage off and on again
and then starting "Reset_Reader"
0xE4FE03
Error in the connection to the reader; the reader is not answering.
The cable between the communications module and reader is wired incorrectly or there is a cable
break
The 24 V supply voltage is not connected or is not on or has failed briefly
Automatic cutout on the communications module has responded
Hardware defect
Another reader is in the vicinity and is active
Execute "init_run" after correcting the error
The antenna of the reader is turned off. A tag command to the communications module was started in
this status.
Turn on the antenna with the command "Antenna on/off."
The antenna is turned on (off) and has received an additional turn-on (turn-off) command
The mode in the "SET_ANT" command is unknown
The antenna on the reader is turned off or the antenna cable is defective
0xE4FE04
The buffer on the communications module or reader is not adequate to store the command temporarily.
0xE4FE05
The buffer on the communications module or reader is not adequate to store the data temporarily.
0xE4FE06
The command is not permitted in this status or is not supported.
0xE4FE07
Startup message from reader/communications module. The reader or communications module was turned
off and has not yet received a "Reset_Reader" ("WRITE_CONFIG") command.
Execute "INIT"
The same physical address in the "IID_HW_CONNECT" parameter is being used more than once.
Check your "IID_HW_CONNECT" parameter settings.
Check connection to the reader
The baud rate was switched over but power has not yet been cycled
0xE4FE81
Reserved
0xE4FE8A
General error
0xE4FE8B
No or bad configuration data was transferred.
106
Ident profile, Add-on instruction for Rockwell systems
Function Manual, 01/2019, C79000-G8976-C410-03