Configuring the instructions

4.1

Importing add-on instructions

To program Ident systems using the Studio 5000 Logix Designer, you require add-on
instructions. You can find the add-on instructions on the DVD supplied with the RF68xR
readers or on the pages of the Siemens Industry Online Support
(https://support.industry.siemens.com/cs/ww/en/ps/14971/dl).
Requirement
The Studio 5000 Logix Designer was started and a project was created.
Procedure
Follow the steps below to import the add-on instructions into the Studio 5000 Logix Designer:
1. Copy the "*.l5x" installation file locally to your PC.
You can find the file on the DVD supplied with the reader or under the provided link.
2. Open the Studio 5000 Logix Designer and change to the project view.
3. Right-click on the folder "Add-on Instructions" in the "Controller Organizer" area.
4. In the shortcut menu, select the menu command "Import Add-On Instruction...".
The dialog "Import Add-On Instruction" opens.
5. Go to the "*.L5X" file and select it.
6. Confirm your entry with "OK".
Result: The add-on instructions are imported into the Studio 5000 Logix Designer:
Ident profile, Add-on instruction for Rockwell systems