Configuring the instructions
4.5 Programming add-on instructions
Table 4- 37
Parameter
PROGRAM
4.5.5.3

Reset_RF200

Figure 4-24
Table 4- 38
Parameter
TAG_CONTROL
TAG_TYPE
RF_POWER
54
Explanation for the instruction "Reset_MV"
Data type
SINT
Instruction "Reset_RF200"
Explanation for the instruction "preset_RF200"
Data type
SINT
SINT
SINT
Default values
Description
Program selection
B#16#0: Reset without program
selection or in the case of diagnos-
tics, the error code for "IN_OP = 0"
is shown at the "STATUS" output
parameter.
B#16#1 ... B#16#0F: Number of
the program to be started
⇒ Reset with program selection
(as of firmware V5.1 of MV400)
Default values
Description
1
Presence check
1
Transponder type:
1 = every ISO transponder
3 = MDS D3xx - optimization
4
Output power; only relevant for
RF290R
RF power from 0.5 W to 5 W in incre-
ments of 0.25 W (range of values:
0x02 ... 0x14).
Default value 0x04 ≙ 1 W.
Ident profile, Add-on instruction for Rockwell systems