Carrier 140/E Series Installation, Start--Up, Operating, And Service And Maintenance page 7

Table of Contents

Advertisement

FIRE, INJURY O R DEATH HAZARD
Failure
t o follow
this warning
could
result
in personal
injury,
death, and/or property
damage.
When
the furnace
is installed
in a residential
garage,
the
burners
and ignition
sources
must
be located
at least
18
inches
(457
mm)
above
the floor.
The furnace
must
be
located
or protected
to avoid damage
by vehicles.
When the
furnace
is installed
in a public
garage,
airplane
hangar,
or
other
building
having
a hazardous
atmosphere,
the furnace
must
be installed
in accordance
with the NFGC.
(See Fig.
5.)
18-IN. (457.2 mm)
MINIMUM TO BURNERS
A93044
Fig. 5 - Installation
in a Garage
FIRE HAZARD
Failure
to follow
this warning
could
result
in personal
injury,
death and/or property
damage.
Do not install the furnace
on its back or hang furnace
with
control
compartment
facing
downward.
Safety
control
operation
will
be
adversely
affected.
Never
connect
return-air
ducts to the back of the furnace.
(See Fig. 60
zt
Fig. 6 - Prohibit Installation on Back
A02054
PROPERTY
DAMAGE
HAZARD
Improper use or installation
of this furnace may cause
premature component failure. This gas furnace may be used
for construction heat provided that:
-The furnace is permanently
installed with all electrical
wiring, piping, venting and ducting installed according to
these installation instructions. A return air duct is provided,
sealed to the furnace casing, and terminated
outside the
space containing
the furnace. This prevents
a negative
pressure condition as created by the circulating air blower,
causing
a flame roll-out
and/or
drawing
combustion
products into the structure.
-The furnace is controlled by a thermostat. It may not be
"hot wired" to provide heat continuously
to the structure
without thermostatic control.
-Clean outside air is provided for combustion. This is to
minimize the corrosive effects of adhesives, sealers and
other
construction
materials.
It
also
prevents
the
entrainment of drywall dust into combustion air, which can
cause fouling and plugging of furnace components.
-The
temperature
of the return air to the furnace
is
maintained between 55°F (13°C) and 80°F (27°C), with
no evening setback or shutdown. The use of the furnace
while the structure is under construction
is deemed to be
intermittent operation per our installation instructions.
-The air temperature rise is within the rated rise range on
the furnace rating plate, and the gas input rate has been set
to the nameplate value.
-The filters used to clean the circulating air during the
construction process must be either changed or thoroughly
cleaned prior to occupancy.
-The furnace, ductwork and filters are cleaned as necessary
to remove drywall dust and construction
debris from all
HVAC system components after construction is completed.
-Verify
proper
furnace
operating
conditions
including
ignition, gas input rate, air temperature rise, and venting
accordin_ to these installation instructions.
LOCATION
RELATIVE
TO COOLING
EQUIPMENT
The cooling coil must be installed parallel with, or on the
downstream side of the unit to avoid condensation in the heat
exchangers. When installed parallel with the furnace, dampers or
other flow control must prevent chilled air from entering the
furnace. If the dampers are manually operated, they must be
equipped with means to prevent operation of either unit unless
the damper is in the full-heat or full-cool position.
AIR FOR COMBUSTION
AND
VENTILATION
Provisions for adequate combustion, ventilation, and dilution air
must be provided in accordance with:
U.S. installations:
Section
9.3 of the NFPA
54 /A ANSI
Z223.1-2009,
Air
for
Combustion
and
Ventilation,
and
applicable provisions of the local building codes.
g

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents