Carrier 140/E Series Installation, Start--Up, Operating, And Service And Maintenance page 32

Table of Contents

Advertisement

/-X
SEE NOTES:
1,2,4,5,7,8,9
Fig. 47 - Horizontal
Right Application-Vent
Elbow
Left
A02068
VENTING
NOTES FOR FIG. 35 - 47
1. For common
vent, vent connector
sizing and vent material:
United
States-use
the NFGC.
2. Immediately
increase
to 5-in.
or 6-in. (127 or 152 ram) vent connector
outside furnace
casing when 5-in. (127 ram) vent connector
is
required,
refer to Note 1 above.
3. Side outlet vent for upflow
and downflow
installations
nmst
use Type B vent immediately
after exiting
the furnace,
except
when
factory-approved
Downflow
Vent Guard
Kit, is used in the downflow
position.
See Table 18 for accessory
listing.
4. Type-B
vent where required,
refer to Note 1 above.
5. Four-in.
(102 ram) single-wall
(26 ga. rain.) vent nmst be used inside furnace
casing and when the factory-approved
Downflow
Vent
Guard
Kit is used external
to the furnace.
See Table 18 for accessory
listing.
6. Accessory
Downflow
Vent Guard
Kit required
in downflow
installations
with lower vent configuration.
See Table 18 for accessory
listing.
7. Chinmey
Adapter
Kit may be required
for exterior
masonry
chinmey
applications.
Refer
to Chinmey
Adapter
Kit for sizing
and
complete
application
details.
See Table 18 for accessory
listing.
8. Secure vent connector
to furnace
elbow with (2) corrosion-resistant
sheet metal screws, spaced
approximately
180 ° apart.
9. Secure
all other single wall vent connector
joints with (3) corrosion
resistant
screws spaced
approximately
120 ° apart. Secure Type-B
vent connectors
per vent connector
manufacturer's
recommendations.
10. The total height
of the vent and connector
shall be at least seven feet (2 M) for the 154,000
Btuh
gas input rate model
when installed
in a downflow
application
with furnace
elbow
turned
to left side with the connector
elbow
outside
furnace
casing
pointing
upward.
(See Fig. 40.)
Caution!!
For the following
applications,
use the minimum
vertical
heights
as specified
below.
For all other applications,
follow
exclusively
the National
Fuel Gas Code
MINIMUM
VENT
MINIMUM
VERTICAL
FURNACE
VENT
FURNACE
DIAMETER
VENT
HEIGHT
ORIENTATION
ORIENTATION
INPUT(BTUH/HR)
IN. (mm)*
FT. (M)**
Vent elbow
left, then
154,000
132,000
5 (127)
12 (3.6)
Downflow
up Fig. 39
110,000
(036/-
12 only)
154,000
Horizontal
Left
132,000
5 (127)
7 (.65)
154,000
Horizontal
Left
162,000
5 (127)
7 (.65)
Horizontal
Left
154,000
5 (127)
7 (.65)
Downflow
110,000
(036/-
12 only)
5 (127)
10 (3.0)
Downflow
110,000
(036/-
12 only)
5 (127)
10 (3.0)
Vent elbow right,
then up Fig. 42
Vent Elbow up Fig.
43
Vent elbow right Fig.
44
Vent elbow up then
left Fig. 37
Vent elbow up, then
right Fig. 40
*4 in. (102 mm) inside casin¢ or vent guard
**Including 4 in. (102 mm) vent section(s)
NOTE: All vent configurations
must also meet National Fuel Gas Code venting requirements
NFGC.
32

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents