Carrier 140/E Series Installation, Start--Up, Operating, And Service And Maintenance page 35

Table of Contents

Advertisement

Table 1 1
- Altitude
Derate Multiplier
for U.S.A.
ALTITUDE
PERCENT
DERATE MULTiPLiER
FT.(M)
OF DERATE
FACTOR*
0-2000
0
1.00
(0- 61O)
2001-3000
8-I2
0.90
(61 O- 914)
3001-4000
12-16
0.86
(914-1219)
4001-5000
16-20
0.82
(1219-1524)
5001-6000
20-24
0.78
1524-1829)
6001-7000
24-28
0.74
(1829-2134)
7001-8000
28-32
0.70
(2134- 2438)
8001-9000
32-36
0.66
(2438-2743)
9001-10,000
36-40
0.62
(2743-3048)
* Derate multiplier factors are based on midpoint altitude for altitude
range.
Low NOx
models
in downflow
or horizontal
positions
MUST
use Table
16 (21,000
BTUH
per burner).
See input
listed
on
rating plate.
a. Obtain average yearly gas heat value (at installed altitude)
from local gas supplier.
b. Obtain average yearly gas specific gravity from local gas
supplier.
c. Find installation
altitude
in Table 15 or 16.
d. Find closest
natural
gas heat value and specific
gravity
in Table 15 or 16.
e. Follow
heat value and specific gravity
lines to point of
intersection
to find orifice size and low-and
high-heat
manifold
pressure
settings
for proper
operation.
f. Check and verify burner
orifice size in furnace.
NEVER
ASSUME
ORIFICE
SIZE.
ALWAYS
CHECK
AND
VERIFY.
g. Replace
orifice with correct
size, if required
by Table 15
or
16.
Use
only
factory-supplied
orifices.
See
EXAMPLE
1.
EXAMPLE
1:(0-2000
ft. / 0-610
M altitude)
For 22,000
Btuh per burner
application,
use Table 15.
Heating
value = 1000 Btuh/cu
ft.
Specific
gravity = 0.62
Therefore:
Orifice No. 43"
Manifold
pressure:
3.7-In.
W.C. for high-heat
1.6-In.
W.C. for low-heat
* Furnace
is shipped
with No. 43 orifices. In this example
all main burner
orifices are the correct size and do not need
to be changed
to obtain
proper input rate.
3. Ac[iust manifold
pressure
to obtain low fire input rate. (See
Fig. 48.)
a. Turn gas valve ON/OFF
switch to OFF.
b. Remove
manifold
pressure
tap plug from gas valve.
c. Connect
a water colunm
manometer
or sinfilar device to
manifold
pressure
tap.
d. Turn gas valve ON/OFF
switch to ON.
A06667
Fig. 48 - Redundant
Automatic
Gas Control
Valve
e. Move setup switch
LHT (SW-1)
on furnace
control
to
ON position
to lock furnace
in low-heat
operation.
(See
Fig.
33 and Table 10.)
f. Manually
close blower
door switch.
g. Jumper
R and W/WI
thermostat
connections
on control
to start furnace.
(See Fig.
33.)
h. Remove
regulator
adjustment
cap from
low-heat
gas
valve pressure
regulators.
(See Fig. 48.) Turn low-heat
adjusting
screw
(3/16 in. (5 ram) or smaller
flat tipped
screwdriver)
counterclockwise
(out)
to decrease
input
rate or clockwise
(in) to increase
input rate.
NOTE:
DO
NOT
set low-heat
manifold
pressure
less than
1.4-In.
W.C.
or more
than
1.7-In.
W.C.
for natural
gas.
If
manifold
pressure
is outside
this
range,
change
main
burner
orifices.
i. Install low-heat
regulator
adjustment
cap.
j. Leave manometer
or sinfilar device
connected
and pro-
ceed to Step 4.
NOTE:
If orifice hole appears
damaged
or it is suspected
to have
been re-drilled,
check
orifice
hole with
a numbered
drill bit of
correct
size. Never
re-drill
an orifice.
A burr-free
and squarely
aligned
orifice
hole is essential
for proper flame characteristics.
4. Verify natural
gas low-heat
input rate by clocking
meter.
NOTE:
Gas valve regulator
adjustment
caps nmst be in place for
proper input to be clocked.
a. Turn off all other gas appliances
and pilots served by the
meter.
b. Run for 3 nfinutes
in low-heat
operation.
c. Measure
time (in sec) for gas meter to complete
I revolu-
tion and note reading. The 2 or 5 cubic feet dial provides
a more accurate
measurement
of gas flow.
35

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents