Carrier 140/E Series Installation, Start--Up, Operating, And Service And Maintenance page 20

Table of Contents

Advertisement

g
115-VOLT FIELD-
SUPPLIED
FUSED
DISCONNECT
....
FIELD 24-VOLT WIRING
....
FIELD 115-, 208/230-, 460-VOLT WIRING
--
FACTORY 24-VOLT WIRING
FACTORY 115-VOLT WIRING
NOTE 2
_
, <j
.zl
,<1
_.u. ,.._
I i(_ i(_) t
@t
1"STAGE
FIVE
THERMOSTAT
FIELD-SUPPLIED
WIRE
_l
!
i
i
!
!
TERM NALS
FUSED DISCONNECT
T HREE-WIRE
HEATING-
ON LY
I
I
I
I
@
O
JUNCTION
@'
BOX
(_
CONTROL
BOX
(_-
24-VOLT
TERMINAL
BLOCK
I
I
I
I
L
I
[
[
"i--
i
i
-.4 .....
4-- ....
4-----b------
[
I
I
I
[
I
I
I
7-.....
i
I
I
'
NOTEI
l
J 1
I
I
i
i !
J
I
L -t_-----
I
J
m,-,
FURNACE
208/230-
OR
460-VOLT
PHASE
=-__---1208/230-
=_.L_rTTL____LVOLT
r _'u
- -I
(SINGLE
--_---_.--.._---
JPHASE
I
-GNDI
CONDENSING
UNIT
NOTES: 1. Connect Y/Y2-terminal as shown for proper operation.
2. Some thermostats require a "C" terminal connection as shown.
3, If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire,
Fig. 23 - Field Wiring
Diagram
A95236
A 1/8-in.
(3 ram) NPT plugged
tapping, accessible
for test gauge
connection,
MUST
be
installed
immediately
upstream
of gas
supply
connection
to
furnace
and
downstream
of
manual
equipment
shutoff valve.
Piping
should
be pressure
and
leak tested
in accordance
with
NFGC in the United
States, local, and national
plumbing
and gas
codes
before
the
furnace
has
been
connected.
After
all
connections
have been made, purge lines and check for leakage
at
furnace
prior to operating
furnace.
If pressure
exceeds
0.5 psig (14-In.
W.C.), gas supply pipe nmst
be disconnected
from
furnace
and capped
before
and during
supply
pipe pressure
test. If test pressure
is equal to or less than
0.5 psig (14-In.
W.C.), turn off electric
shutoff switch
located
on
furnace
gas
control
valve
and
accessible
manual
equipment
shutoff
valve before
and during
supply
pipe pressure
test. After
all connections
have
been
made,
purge
lines
and
check
for
leakage
at furnace prior to operating
furnace.
The
gas
supply
pressure
shall
be
within
the
maximum
and
minimum
inlet supply
pressures
marked
on the rating
plate with
the furnace
burners
ON and OFF.
ELECTRICAL
CONNECTIONS
ELECTRICAL
SHOCK
HAZARD
Failure
to follow
this warning
could
result
in personal
iniury or death.
Blower
access
panel
door
switch
opens
l15-v
power
to
control.
No component
operation
can occur. Do not bypass
or close switch with panel removed.
See Fig. 23 for field wiring
diagram
showing
typical
field 115-v
wiring.
Check
all factory
and
field electrical
connections
for
tightness.
Field-supplied
wiring
shall conform
with the linfitations
of 63 °F
(33 ° C) rise.
ELECTRICAL
SHOCK
AND FIRE HAZARD
Failure
to follow
this warning
could
result
in personal
iniury,
death, or property
damage.
The
cabinet
MUST
have
an uninterrupted
or unbroken
ground
according
to NEC ANSI/NFPA
70-2008
or local
codes
to nfininfize
personal
iniury
if an
electrical
fault
should
occur.
This may consist
of electrical
wire,
conduit
approved
for electrical
ground
or a listed, grounded
power
cord
(where
pernfitted
by local
code)
when
installed
in
accordance
with
existing
electrical
codes.
Refer
to
the
power
cord manufacturer's
ratings
for proper
wire gauge.
Do not use gas piping
as an electrical
ground.
FURNACE
MAY NOT
OPERATE
HAZARD
Failure to follow this caution may result in internfittent
furnace operation,
Furnace control must be grounded for proper operation or
else control will lock out. Control nmst remain grounded
through green/yellow wire routed to gas valve and manifold
bracket screw,
l15-V
WIRING
Verify that the voltage,
frequency,
and phase
correspond
to that
specified
on unit rating
plate. Also,
check to be sure that service
provided
by utility
is sufficient
to handle
load imposed
by this
equipment.
Refer
to
rating
plate
or Table
7 for
equipment
electrical
specifications.
20

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents