7.1.3.2
SICAM Q80 7KG8080 configuration as PPP-Server
Your device can be configured as a PPP server. The program IF-Config, which is installed along with the SICAM Q80
Manager software and is located in the SICAM Q80 7KG8080 program group, is provided for the purpose of making
this configuration.
For the PPP-configuration, the device must be connected with the PC via Ethernet. Start the program IF-Config.
Select your device in the tree diagram on the left side in the manner customary for working with the MS-Explorer.
When the diagram expands, a network search is automatically carried out via the respective adapter. Among the
entries under the expanded branch for your device, click on Modem.
On the dialog's right side, you can then make all the PPP-setting necessary for running the device as a PPP-server.
You can read more on this in the next segment:
To write the settings to the measurement device unit, simply click on the device's entry on the left side of the dialog
and then on the button Apply on the right side. But first check the settings in the controls above and activate/
deactivate them as appropriate.
Once the configuration has been written to the device, it performs a warm start and applies the new settings. This
procedure lasts approx. 1-2min. When the text "Settings applied" appears in the box Messages, configuration of your
device is complete and you can proceed with the next device.
7.1.3.3
Modem settings for TCP/IP devices (PPP)
To set the PPP-parameters, click on the button PPP-settings in the main dialog.
IP-address: since Windows isn't able to assign an IP-address to SICAM Q80 7KG8080, an IP-address must be
entered in the box Local IP-address (device). The second box, Remote IP-address (caller) can be left on 0.0.0.0. In
this case, an IP-address must be assigned to the caller (PC) by means of the Dial-Up network settings. This IP-
address must be located in the same subnet as the address assigned to SICAM Q80 7KG8080. Observe the notes
under
Computers with multiple TCP/IP
Security: These options govern the protection against unauthorized access to the SICAM Q80 7KG8080 unit.
Modem settings for TCP/IP devices (PPP)
.
204
Maximum packet size: This option enables reduction of the maximum package
size in order to improve data throughput if the connection is poor. The default
value of "1500" should only be reduced if the telephone connection is very poor,
having many CRC-errors. Depending on the version of Windows, CRC-errors are
indicated either in the status of the Dial-up connection or in the system monitor.