Table 11.3 Faults with the output circuit and the corrective actions (continued)
Situation
The load which
was turned off
is turned on for
Example
a moment at
6
power-off.
(Transistor
output)
Cause
The load [2] which was turned off may be turned on due to
back electromotive force at the time of power-off [1] if an
inductive load is used.
Output module,
combined module
Source output
ON
OFF
Output module,
combined module
Sink output
ON
OFF
[3]
Back electromotive
force
Load
TB1 ON
[2]
TB2 OFF
Load
[1]
Shut off
COM+
CTL-
[3]
Back electromotive
force
Load
TB1 ON
[2]
TB2 OFF
Load
[1]
Shut off
COM-
CTL+
11 - 27
Countermeasure
To prevent the generation of the back
electromotive force, connect diode in
parallel with load where the back
electromotive force has been generated.