Siemens Simatic Ident Function Manual page 90

Rfid systems ident profile and ident blocks, standard function for ident systems
Hide thumbs Also See for Simatic Ident:
Table of Contents

Advertisement

Setting parameters for blocks
3.5 Programming the Ident profile
Structure of the configuration data attachment of "WRITE-CONFIG"
For RF61xR/RF68xR and RF18xC:
● When CONFIG = 0x01:
Reset_Reader; LEN_DATA = 0x00
● When CONFIG = 0x03:
When replacing a module, it is possible to read all the configuration data from the
CM/reader and to store it on the controller. When the module is replaced, this data can
then be loaded on the reader from the controller. The command "WRITE-CONFIG" (0x03)
is used for the download to the CM/reader and "READ-CONFIG" for the upload from the
reader.
LEN_DATA = Size of the configuration data + 6 bytes
● When CONFIG = 0x80:
The structure of the send buffer corresponds to that of the block "Set_Param (Page 45)".
LEN_DATA = 0x08
For RF200, RF300, RF620R, RF630R, MOBY D/U
Table 3- 74
For RF200, RF300, RF620R, RF630R, MOBY D/U when "CONFIG = 0x03"
Byte
1
2...5
1)
Value
0x04
0x00
In the communications module RF180C as of V2.2 in conjunction with MOBY U byte 4 is preset with the calendar week
1)
and 5 with the year.
With the readers named in the title of the table the value "0x0A" (LEN_DATA = 0x10) is used in byte 6. In the MOBY I
2)
migration in RF300 readers of the second generation the value "0x05" (LEN_DATA = 0x0B) is used.
90
Byte
0
2
6
10 ... end "DATA"
6
7...8
9
2)
0x0A
0x00
scanning_
0x05
time
Name
Structure identifier (2 bytes)
Length information (4 bytes)
Length of the version identifier and parameter block
Version identifier (4 bytes)
Based on the identifier, you can uniquely identify the configuration.
This is a time stamp in Linux format.
The time stamp indicates how many seconds have passed since
January 1, 1979, 00:00 (midnight). The identifier is assigned when a
configuration is generated.
Parameter block
10
11
12
param
op-
distance_
tion_1
limiting
Ident profile and Ident blocks, standard function for Ident systems
Function Manual, 10/2018, C79000-G8976-C387-04
13...14
15
16
No. of
field_on_
field_on_
tran-
control
time
sponders