Error messages
4.3 Errors from the communications module/reader
Error mes-
Description
sage
(hex)
0xE6FE0300
Bad parameter assignment of the communications module or reader
Check "INPUT" parameter in the Ident profile.
Check parameter settings in HW Config / TIA Portal.
"WRITE-CONFIG" command has incorrect parameter settings.
After a startup, the reader or communications module has still not received an "INIT".
The parameter assignment of the reader or communications module on PROFIBUS/PROFINET was
incorrect and the command cannot be executed.
Length of the input/output areas too small for the cyclic I/O word.
Correct GSD file being used?
User data length set with command (e.g. "READ") too high.
Error when processing the command
Bad data in the "AdvancedCmd" or "IID_CMD_STRUCT" (e.g. "WRITE" command with length = 0);
check "AdvancedCmd" or "IID_CMD_STRUCT" and execute "INIT".
Reader/communications module hardware defective: The reader or communications module re-
ceives bad data with "INIT".
AB byte does not comply with the useful data length.
Wrong reset block was selected.
Use the reset block suitable for the Ident device.
Technology object with RF68xR and RF120C: Regardless of the selected Ident device/system, use
the "Reset_Reader" function block.
0xE6FE0400
Presence error:
A transponder has passed by a reader without being processed by a command.
This error message is not reported immediately. Instead, the reader or communications module is
waiting for the next command (read, write). This command is immediately replied to with this error. This
means that a read or write command is not processed. The next command is executed normally again
by the reader/communications module.
An "INIT" from the Ident profile also resets this error status.
Bit 2 is set in the OPT1 parameter and there is no transponder in the transmission window.
0xE6FE0500
An error has occurred that makes a Reset_Reader ("WRITE-CONFIG" with "Config = 3") necessary.
The "WRITE-CONFIG" command is incorrect.
Start "INIT" after correcting the error
Check the parameter "IID_HW_CONNECT".
0xE6FE8100
A parameter is missing.
0xE6FE8200
The parameter has an invalid format.
0xE6FE8300
The parameter type is invalid.
0xE6FE8400
Unknown parameter
0xE6FE8500
The command or the frame has an invalid format.
0xE6FE8600
The inventory command failed.
0xE6FE8700
Read access to the transponder has failed.
0xE6FE8800
Write access to the transponder has failed.
0xE6FE8900
Writing the EPC-ID on the transponder has failed.
128
Ident profile and Ident blocks, standard function for Ident systems