Error messages

4.2 STEP 7 - error messages

4.2
STEP 7 - error messages
If you have inserted the blocks and data types in your project and you encounter problems
during compilation, please check the following points:
● The block name, the block number and the data type name must not be changed.
● The content of the data types "IID_CMD_STRUCT" and "IID_HW_CONNECT" must not
be changed. The content may only be adapted when these have been linked into a data
block as variables.
● If you use the Ident blocks, the data types "IID_HW_CONNECT" and
"IID_CMD_STRUCT" and the block "Ident_Profile_1KB" must always exist in your project.
4.3

Errors from the communications module/reader

The causes of these errors can, for example, be as follows:
● Errors have occurred in communication between the CM and the reader or between the
reader and the transponder.
● The communications module is unable to process the command.
Byte 3 of the "STATUS" is not relevant for the error messages.
Table 4- 2
Error messages from communications module/reader or from the Ident profile via the "STATUS" output pa-
rameter
Error mes-
Description
sage
(hex)
0xE1FE0100
Memory of the transponder cannot be written to
Transponder memory is defective
Transponder EEPROM was written too frequently and has reached the end of its service life
Transponder is write protected (Memory Lock)
0xE1FE0200
Presence error: The transponder has moved out of the transmission window of the reader. The command
was executed only partially.
Read command: "IDENT_DATA" has no valid data.
Write command: The transponder that has just left the antenna field contains an incomplete data record.
Operating distance from reader to transponder is not being maintained
Configuration error: The data record to be processed is too large (in dynamic mode)
With timeout: No transponder in the antenna field
0xE1FE0300
Address error
The address area of the transponder has been exceeded.
Start address of the command start has been incorrectly set
Transponder is not the correct type
Attempted write access to write-protected areas
122
Ident profile and Ident blocks, standard function for Ident systems