Installation Information
Table H. UPS Cabinet Power Cable Terminations 9390-- 80/40 and 9390-- 80/80 kVA
480V/480V
Terminal Function
AC Input to UPS Rectifier
p
and Bypass
(Single Input)
(Single Input)
AC Input to UPS Rectifier
p
(Dual Input)
AC Input To Bypass (Dual
p
Input)
Single Feed Jumper from
g
Rectifier Input Terminals to
Bypass Input Terminals
Bypass Input Terminals
AC Output to
p
Critical Load
C
DC Input from
p
Battery to UPS
Input and Output Neutral
Customer Ground
NOTE: Customer ground, size 2/0, can be
run in any conduit listed in Table I.
A-10
Terminal
E6
E7
E8
E1
E2
E3
yp
(
E6
E7
E8
p
E9
E10
E11
E4
S
E5
E12
Ground
Powerware
9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev A
®
Size of Pressure
Termination
Function
Phase A
1 --- #14---2/0
Phase B
1 --- #14---2/0
Phase C
1 --- #14---2/0
Phase A
1 --- #14---2/0
Phase B
1 --- #14---2/0
Phase C
1 --- #14---2/0
Phase A
1 --- #14---2/0
Phase B
1 --- #14---2/0
Phase C
1 --- #14---2/0
Phase A
N/A
Phase B
N/A
Phase C
N/A
Phase A
1 --- #14---2/0
Phase B
1 --- #14---2/0
Phase C
1 --- #14---2/0
Positive
1 --- #6---500 kcmil
Negative
1 --- #6---500 kcmil
Neutral
4 --- #14---1/0
Ground
8 --- #14---1/0
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201535---5
REVISION:
A
Tightening Torque
Type
Nm (lb in)
Screw
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
5.6 (50)
1/4–20 Hex Nut
5.6 (50)
1/4–20 Hex Nut
5.6 (50)
1/4–20 Hex Nut
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
56.5 (500)
1/2 in. Hex
56.5(500)
1/2 in. Hex
5.6 (50)
Slotted
5.6 (50)
Slotted
SHEET:
DATE:
062504
4 of 7