11. If you are installing multiple REPO stations, wire additional stations in parallel with
the first REPO.
12. If required, install wiring from the REPO station to trip circuitry of upstream
protective devices. A normally-open contact is provided between terminals 6 and 7
of REPO, as shown in Figure 5-1. REPO switch wiring must be in accordance with
UL Class II requirements.
13. When all wiring is complete, reinstall safety shield panels removed in previous
steps.
14. Close door and secure with latch.
Installing a Remote Emergency Power-Off Control