Tables, data records

3.4 Tables, PROFINET data records

3.4
Tables, PROFINET data records
3.4.1

PROFINET tables

3.4.1.1

OPC UA variables

Node IDs
The name of the variable is composed of the namespace ID2 and the node ID as follows:
ns=http://siemens.com/automation/simocode/provpn;i=Node ID of the relevant variable.
Example:
You want to access the maximum motor current. You search for the node ID of the variable
"Max. Current I_max" in the following table: Node ID=33
Table 3- 45
Node IDs (1)
Node ID
Data type
Acyclic receive
11
Boolean
12
Boolean
13
Boolean
14
Boolean
15
Boolean
16
Boolean
17
Boolean
18
Boolean
19
Boolean
20
Boolean
21
Boolean
22
Boolean
23
Boolean
24
Boolean
25
Boolean
26
Boolean
27
Unsigned word
Measured values
30
Unsigned byte
31
Unsigned byte
32
Unsigned byte
33
Unsigned word
34
Unsigned word
202
Description
Acyclic receive - Bit 0.0
Acyclic receive - Bit 0.1
Acyclic receive - Bit 0.2
Acyclic receive - Bit 0.3
Acyclic receive - Bit 0.4
Acyclic receive - Bit 0.5
Acyclic receive - Bit 0.6
Acyclic receive - Bit 0.7
Acyclic receive - Bit 1.0
Acyclic receive - Bit 1.1
Acyclic receive - Bit 1.2
Acyclic receive - Bit 1.3
Acyclic receive - Bit 1.4
Acyclic receive - Bit 1.5
Acyclic receive - Bit 1.6
Acyclic receive - Bit 1.7
Acyclic receive - analog value
Thermal memory
Phase unbalance
Cos phi
Max. current I_max
Current I_L1
Function Manual, 11/2018, A5E40508495002A/RS-AC/003