Solenoid Valve - Siemens SIMOCODE pro Function Manual

Industrial controls, motor management and control devices, communication
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Tables, data records
3.2 Assignment of cyclic receive and send data for predefined control functions
3.2.11

Solenoid valve

Table 3- 14
Assignment of cyclic receive/send data, solenoid valve
Cyclic receive data
Bit 0.0
Bit 0.1
Bit 0.2
Bit 0.3
Bit 0.4
Bit 0.5
Bit 0.6
Bit 0.7
Bit 1.0
Bit 1.1
Bit 1.2
Bit 1.3
Bit 1.4
Bit 1.5
Bit 1.6
Bit 1.7
Byte 2/3 *) (analog value)
Cycl. send data
Bit 0.0
Bit 0.1
Bit 0.2
Bit 0.3
Bit 0.4
Bit 0.5
Bit 0.6
Bit 0.7
Bit 1.0
Bit 1.1
Bit 1.2
Bit 1.3
Bit 1.4
Bit 1.5
Bit 1.6
Bit 1.7
Byte 2/3 (analog value)
Byte 4/5 *) (analog value)
Byte 6/7 *) (analog value)
Byte 8/9 *) (analog value)
*) for SIMOCODE pro V / pro S, basic type 1 only
138
Not connected
Device parameters → Motor control → Control stations → PLC/PCS [DP] → Close
Device parameters → Motor control → Control stations → PLC/PCS [DP] → Open
Further function blocks → Standard functions → Test / Reset → Test1 - Input
Not connected
Device parameters → Motor control → Control stations → Mode selector S1
Further function blocks → Standard functions → Test / Reset → Reset 1 → Input
Not connected
Not connected
Not connected
Not connected
Not connected
Not connected
Not connected
Not connected
Not connected
Not connected
Not connected
Status - OFF (CLOSED)
Status - ON > (OPEN)
Not connected
Not connected
Status - Remote mode
Status - General fault
Status - general warning
Not connected
Not connected
Not connected
Not connected
Not connected
Not connected
Not connected
Not connected
Not connected
Not connected
Not connected
Not connected
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003