Siemens SIMOCODE pro Function Manual page 55

Industrial controls, motor management and control devices, communication
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Configuring device names with SIMOCODE ES parameterization software and downloading
to the device
In this case, the device name must be configured under "PROFINET Parameters → Station"
and the "Overwrite device name in device" parameter must be active.
Note
Transferring the device parameters
It is always possible to transfer the device parameters via the system interface.
If the PROFINET IO device name has already been configured in a different way, the device
parameters can be transferred via PROFINET, too.
Note
Assignment of the device name
The device name can be assigned with the "SIMOCODE ES" parameterization software in
the Online & Diagnostic Functions. This function is not identical with parameterization with
the "PROFINET parameter" dialog box. Unlike in this dialog box, under "PROFINET
Parameters → Station," the "Overwrite device name in device" parameter must not be active.
Note
Changing the device name
Every change to the device name with SIMOCODE ES in the "PROFINET Parameters"
dialog box requires a restart of the communication interface. A new start interrupts all
Ethernet and PROFINET links and reestablishes them afterward.
1. Device is given a technological name (device name here: Motor-1)
2. Configuration is loaded into the IO controller
3. Configuration of device names and IP parameters with SIMOCODE ES:
a) Device name "Motor-1" is configured with SIMOCODE ES and is transferred into the
device via the system interface / PROFINET
b) Device name and IP parameter are configured with SIMOCODE ES and are
transferred into the device via the system interface / PROFINET
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Communication
2.2 PROFINET communication
55