Siemens SIMOCODE pro Function Manual page 304

Industrial controls, motor management and control devices, communication
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Tables, data records
3.5 Modbus data tables
Input/holding register
Address high/
Bit
low
0x4387
0-1
high
2-3
4-5
6-7
low
0-1
2-3
4-5
6-7
0x4388
high
0-1
2-3
4-5
6-7
low
0-1
2-3
4-5
6-7
0x4389
high
0-1
2-3
4-5
6-7
low
0-1
2-3
4-5
304
Designation
Type Range
Reserved
Bit[2]
Reserved
Bit[2]
Reserved
Bit[2]
AM1 - active inputs
Bit[2] 0, 1, 2
DM - Input delay
Bit[2] 0 ... 3
AM1 - Response to
Bit[2] 1, 2, 3
open circuit
EM - response to an
Bit[2] 1, 3
external ground fault
EM - response to
Bit[2] 0, 1, 2
warning of an
external ground fault
Reserved
Bit[2]
Reserved
Bit[2]
DM-F - Test
Bit[2] 0, 1, 2
requirement
response
DM-F - safety-
Bit[2] 0, 1, 2, 3
related tripping
response
TM1 - Trip
Bit[2] 1, 3
response T>
TM1 - Warning
Bit[2] 0, 1, 2
response T>
TM1 - Response to
Bit[2] 0, 1, 2, 3
a sensor fault / out
of range
TM1 - active sensors Bit[2] 0, 1, 2
Trip response P>
Bit[2] 0, 1, 3
Warning response
Bit[2] 0, 1, 2
P>
Trip response P<
Bit[2] 0, 1, 3
Warning response
Bit[2] 0, 1, 2
P<
Trip response
Bit[2] 0, 1, 3
cos phi <
Warning response
Bit[2] 0, 1, 2
cos phi <
Trip response U<
Bit[2] 0, 1, 3
Unit
Default Comments
0
0
0
0
0 = 1 input
1 = 2 inputs
2 = 3 inputs
10
1
Offset 6 ms
ms
2
0 = Disabled
1 = Signaling
1
2 = Warn
3 = Tripping
0
0
0
0
0
3
2
2
2*)
0 = 1 sensors
1 = 2 sensors
2 = 3 sensors
0
0 = Disabled
1 = Signaling
0
2 = Warn
0
3 = Tripping
0
0
0
0
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
Access
Info
1)
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
SIMOCODE pro - Communication

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents