6.2
Replacing batteries
When to replace
When the transmitter displays a LO BATT message you have 2-4 weeks to replace both batteries before
they expire. When batteries are removed or expired, all transmitter data is retained in the transmitter's non-
volatile memory.
Tools required
•
#1 Phillips Screwdriver or 1/8" Slotted Screwdriver
•
Torque Screwdriver
•
1.5 mm hex key
Procedure
ATTENTION
Batteries must be replaced only by a trained service technician.
WARNINGS
•
•
•
SHOCK HAZARD
Depending on your installation, transmitter input wiring sources may contain
high voltage. Disconnect all power from transmitter input sources before
accessing the batteries. Failure to do so could result in death or serious injury
if the input terminals or wires are accidentally touched.
Rev. 3
OneWireless XYR 6000 Temperature and Temperature/Discrete Input Transmitter User's Manual
6/24/08
Description
COAX CABLE ASSY, 1.0M ( 3.3 Ft) LONG, N-MALE - N-MALE
COAX CABLE ASSY, 3.0M (10.0 Ft) LONG, N-MALE - N-MALE
COAX CABLE ASSY, 10.0M (33.0 Ft) LONG, N-MALE - N-MALE
LIGHTNING SURGE ARRESTOR
BATTERY HOLDER, PRESSURE
BATTERY HOLDER, TEMPERATURE, HLAI, CORROSION
3.6V LITHIUM THIONYL CHLORIDE (Li-SOCI2) BATTERY
3.6V LITHIUM THIONYL CHLORIDE (Li-SOCI2) BATTERY
3.6V LITHIUM THIONYL CHLORIDE (Li-SOCI2) BATTERY
Risk of death or serious injury by explosion. Do not open transmitter
enclosure when an explosive gas atmosphere is present.
Batteries must not be changed in an explosive gas atmosphere.
The batteries used in this device may present a risk of fire or chemical
burn if mistreated. Do not recharge, disassemble, heat above 100°C
(212°F), or incinerate.
6. Maintenance/Repair
6.2. Replacing batteries
37