Table 14 Sensor Module Replacement; Figure 9 Sensor Module Removal And Replacement - Honeywell OneWireless XYR 6000 User Manual

Temperature and temperature/discrete input transmitter
Hide thumbs Also See for OneWireless XYR 6000:
Table of Contents

Advertisement

6. Maintenance/Repair
6.3. Replacing sensor module
Step
Honeywell recommends that the transmitter be removed from service and moved to a clean
1
area before servicing.
Loosen the M3 locking set screw on the display end-cap. See item 1 in Figure 9. Unscrew and
2
remove the end cap.
Loosen the two screws on the sensor module. See items 2 in Figure 9.
3
Disconnect each connector on the sensor module. See items 3 in Figure 9.
4
Install new sensor module. Be sure to orient sensor module in the proper viewing orientation
5
before tightening two sensor compartment screws.
Reverse steps 1-4.
Torque screws to 0,4 – 0,6 N-M (3.5 – 5.3 Lb-in).
Honeywell recommends lubricating the end cap O-ring with a Silicone Grease such as Dow
Corning #55 or equivalent before replacing the end cap.
Clean the transmitter's nameplate and affix WBSN label over the existing WBSN (Wireless
6
Builder Serial Number).
Return transmitter to service.
7
40
OneWireless XYR 6000 Temperature and Temperature/Discrete Input Transmitter User's Manual

Table 14 Sensor module replacement

3

Figure 9 Sensor module removal and replacement

Action
3
2
2
1
Rev. 3
6/24/08

Advertisement

Table of Contents
loading

Table of Contents