5. Operation
5.3. Transmitter PV display
PV status
(blank)
BAD
UNC
Transmitter
Wireless Builder display
display
OUT SVC
OOS
CAL ERR
Calibration Error
CFG ERR
Configuration Error
LOW BAT
Low Battery
NO RADIO
Radio Interprocessor
Comm Error
CJ FAIL
CJ Failure
BAD RADIO
Sensor Radio SPI
SPI
Communication Failure
24
OneWireless XYR 6000 Temperature and Temperature/Discrete Input Transmitter User's Manual
Table 7 PV status
•
PV is normal – no action required
•
Possible calibration error – Clear calibration
Transducer Block can not execute due to internal firmware state – Attempt
•
cold restart of device.
Transducer Block can not execute due to hardware fault – Replace sensor
•
module. See page 36.
Sensor failure – Check the following.
•
−
connection between sensor board and terminal block
−
field wiring terminations on the terminal block
field sensor
−
•
Warning: Input inaccurate due to uncertain input data integrity.
•
Warning: Input inaccurate due to input conversion limitations or resolution.
Warning: Input outside of characterized range. Value is estimated.
•
Table 8 Device status
Definition
All channels are out of
service.
Calibration Data Invalid
or could not be read.
Configuration Check
Error.
Battery Voltage Critically
Low
Radio Board is not
accessible.
Cold junction failure
Radio detected loss of
communication with
sensor board over the
inter-processor
communication link.
Cause – Action
What to do
Restore mode to Auto in Wireless
Builder.
Use Cal Clear, Restore, or User
Calibrate.
Database is corrupted. Cold start
and reload configuration.
Replace batteries as soon as
possible. See page 37.
Restart both the radio and sensor.
If condition persists, replace
sensor module. See page 36.
Check connectors on Terminal
Board and sensor module.
Replace terminal board. See page
44.
Restart both the radio and sensor.
If condition persists, replace
sensor module. See page 36.
Rev. 3
6/24/08