Trane IntelliPak Programming Manual page 80

With symbio 800, 20 to 75 ton with the tracer td7 display
Table of Contents

Advertisement

Troubleshooting
Diagnostic Name
Affects
and Source
Target
Comm Loss:
Unit
Return Air
Isolation Damper
Comm Loss:
Return Air
Isolation Damper
Comm: RA Iso
Damper
Comm Loss:
Unit
Condensate
Overflow
Comm Loss:
Condensate
Overflow
Comm:
Condensate
Overflow
Comm Loss:
Unit
Outdoor Air
Damper
Comm Loss:
Outdoor Air
Damper
Comm: OA
Damper
Comm Loss:
Unit
Outdoor Air
Damper
Feedback
Comm Loss:
Outdoor Air
Damper
Feedback
Comm: OA
Damper
Feedback
Comm Loss:
Unit
Relief Air Damper
Comm Loss:
Relief Air Damper
Comm: Relief
Damper
Comm Loss:
Unit
Relief Air Damper
Feedback
Comm Loss:
Relief Air Damper
Feedback
Comm: Relief
Damper
Feedback
Comm Loss:
Unit
Staged Electric
Heat Relay 1
Comm Loss:
Staged Electric
Heat Relay 1
Comm: Staged
Elec Heat Relay
80
Severity
Persistence
Immediate
Latching
Shutdown
Immediate
Latching
Shutdown
with
Special
Action
Warning with
Non- Latching All
Special Action
Warning with
Non- Latching All
Special Action
Warning with
Non- Latching All
Special Action
Warning
Non- Latching All
Normal
Latching
Shutdown
Active
Modes
Criteria
[Inactive
Modes]
All
Continual loss of communication between the MP and the
Return Air Isolation Damper has occurred for a 30 second
period.
All
Continual loss of communication between the MP and the
Condensate Overflow status has occurred for a 30 second
period.
VOM Behavior: During VOM this diagnostic changes
behavior to a latching warning diagnostic. See the
Condensate Overflow Protection specification for more
information.
Continual loss of communication between the MP and the
Outdoor Air Damper has occurred for a 30 second period.
Disable Economizer function.
Continual loss of communication between the MP and the
Outdoor Air Damper Feedback has occurred for a 30
second period.
Disable Economizer function.
Continual loss of communication between the MP and the
Relief Air Damper has occurred for a 30 second period.
Disable Space Pressure Control.
Continual loss of communication between the MP and the
Relief Air Damper Feedback has occurred for a 30 second
period.
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Reset
Level
Remote
Remote
Remote
Remote
Unit
Unit
Remote
RT-SVP011A-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents