Trane IntelliPak Programming Manual page 57

With symbio 800, 20 to 75 ton with the tracer td7 display
Table of Contents

Advertisement

Diagnostic Name
Affects
and Source
Target
VFD Fault
Circuit
Condenser Fan -
Cktx
VFD Fault
Condenser Fan -
Cktx
VFD Fault
Condenser Fan
VFD Condenser
Circuit
Fan Motor
Current Overload
– Cktx
VFD Condenser
Fan Motor
Current Overload
- Cktx
VFD Cond Fan
Current Ovld
VFD Condenser Fan
Circuit
Ground Fault - Cktx
VFD Condenser Fan
Ground Fault - Cktx
VFD Cond Fan
Ground Fault
VFD Condenser Fan
Circuit
Short Circuit - Cktx
VFD Condenser Fan
Short Circuit - Cktx
VFD Cond Fan
Short Circuit
RT-SVP011A-EN
Severity
Persistence
Warning
Latching
with
Special Action
Warning
Latching
with
Special Action
Warning
Latching
with
Special Action
Warning
Latching
with
Special Action
Active
Modes
Criteria
[Inactive
Modes]
All
VFD Fault. Numerous drive faults can cause this general
fault. Reference the TR170 Installation and Operating
manual for a list of fault codes and descriptions.
Condenser fan control will revert to fixed-speed fan
algorithm using remaining fans.
The Latching behavior for this diagnostic is latched in the
drive. When the drive diagnostics are reset this
diagnostic will be cleared in the Symbio 800 controller.
All
The inverter peak current of approximately 200% of rated
current was exceeded for 1.5 seconds. Condenser fan
control will revert to fixed-speed fan algorithm using
remaining fans.
The Latching behavior for this diagnostic is latched in the
drive. When the drive diagnostics are reset this diagnostic
will be cleared in the Symbio 800 controller.
This drive alarm may be Trip Locked at the TR170 drive.
If the drive determines that the condition could cause
damage to the drive, the drive protects itself by
generating a Trip Lock that can only be cleared by cycling
power.
All
An earth ground fault has resulted in a discharge from the
output phases to ground, either in the cable between the
adjustable frequency drive and the motor or in the motor
itself. Condenser fan control will revert to fixed-speed fan
algorithm using remaining fans. Further operation of the
failed fan is not recommended until measurements to
ground can be taken from the motor leads and the ground
fault removed.
The Latching behavior for this diagnostic is latched in the
drive. When the drive diagnostics are reset this
diagnostic will be cleared in the Symbio 800 controller.
This drive alarm may be Trip Locked at the TR170 drive.
If the drive determines that the condition could cause
damage to the drive, the drive protects itself by
generating a Trip Lock that can only be cleared by cycling
power.
All
A short circuit in the motor windings or the motor terminals was
detected. Condenser fan control will revert to fixed-speed fan
algorithm using remaining fans. Further operation of the failed fan
is not recommended until the short circuit is removed.
The Latching behavior for this diagnostic is latched in the
drive. When the drive diagnostics are reset this
diagnostic will be cleared in the Symbio 800 controller.
This drive alarm may be Trip Locked at the TR170 drive.
If the drive determines that the condition could cause
damage to the drive, the drive protects itself by
generating a Trip Lock that can only be cleared by cycling
power.
Troubleshooting
Reset
Level
Local
Local
Local
Local
57