Trane IntelliPak Programming Manual page 58

With symbio 800, 20 to 75 ton with the tracer td7 display
Table of Contents

Advertisement

Troubleshooting
Diagnostic Name
Affects
and Source
Target
VFD Condenser
Unit
Fan In Hand Mode
– Cktx
VFD Condenser
Fan In Hand Mode
– Cktx
VFD Cond In
Hand Mode
VFD Fault
Cprsr
Compressor –
Cprsr1A
VFD Fault
Compressor -
Cprsr1A
VFD Fault –
Cprsr1A
VFD Compressor
Cprsr
Current Overload
– Cprsr1A
VFD Comp
Current Overload
– Cprsr1A
VFD Comp
Current Ovld
VFD Compressor
Circuit
Ground Fault–
Cprsr1A
VFD Compressor
Ground Fault–
Cprsr1A
VFD Comp
Ground Fault
58
Severity
Persistence
Warning
Non-latching
Immediate
Latching
Shutdown
Immediate
Latching
Shutdown
Immediate
Latching
Shutdown
Active
Modes
Criteria
[Inactive
Modes]
All
The drive has been put into hand mode at the drive
interface. This will cause issues for normal sequences
and operation
Cprsr
VFD Fault. Numerous drive faults can cause this general
Energized
fault including High Pressure Cutout for VFD
compressors. See Service Literature xxxx for a list of fault
codes and description.
The Latching behavior for this diagnostic is latched in the
drive. When the drive diagnostics are reset this
diagnostic will be cleared in the Symbio 800 controller.
Cprsr
The inverter peak current of approximately 200% of rated
Energized
current was exceeded for 1.5 seconds.
This is a drive enforced lockout.
NOTE: There is Drive behavior that results from a Drive
Overcurrent where the drive continues to operate at
reduced RPM
The Latching behavior for this diagnostic is latched in the
drive. When the drive diagnostics are reset this
diagnostic will be cleared in the Symbio 800 controller.
This drive alarm may be Trip Locked at the TR200 drive.
If the drive determines that the condition could cause
damage to the drive, the drive protects itself by
generating a Trip Lock that can only be cleared by cycling
power.
Cprsr
An earth ground fault has resulted in a discharge from the
Energized
output phases to ground, either in the cable between the
adjustable frequency drive and the motor or in the motor
itself. Further compressor operation is not recommended
until measurements to ground can be taken from the
motor leads and the ground fault removed.
The Latching behavior for this diagnostic is latched in the
drive. When the drive diagnostics are reset this
diagnostic will be cleared in the Symbio 800 controller.
This drive alarm may be Trip Locked at the TR200 drive.
If the drive determines that the condition could cause
damage to the drive, the drive protects itself by
generating a Trip Lock that can only be cleared by cycling
power.
Reset
Level
Local
Local
Local
Local
RT-SVP011A-EN