Trane IntelliPak Programming Manual page 67

With symbio 800, 20 to 75 ton with the tracer td7 display
Table of Contents

Advertisement

Diagnostic Name
Affects
and Source
Target
Starts/Hours
Cprsr
Modified -
Cprsrxy
Starts/Hours
Modified -
Cprsrxy
Starts/Hours
Modified - Cprsrxy
High Compressor
Circuit
Press Differential
Cktx
High Compressor
Press Differential
Ckt1
High Cprsr Press
Diff x
High Compressor
Circuit
Press Diff Lockout
Cktx
High Compressor
Press Diff Lockout
Cktx
High Cprsr Press
Diff Lock x
Unit Not
Unit
Economizing
When It Should
Unit Not
Economizing
When It Should
Unit Not Econ
When It Should
Unit Economizing
Unit
When It Should
Not
Unit Economizing
When It Should
Not
Unit Econ When It
Should Not
Outdoor Air
Unit
Damper Not
Modulating
Outdoor Air
Damper Not
Modulating
OA Damper Not
Modulating
Excessive
Unit
Outdoor Air
Excessive
Outdoor Air
Excessive
Outdoor Air
RT-SVP011A-EN
Severity
Persistence
Warning
Non-Latching All
Immediate
Non -Latching Ckt
Shutdown
Immediate
Latching
Shutdown
Warning
Non- Latching Cooling w/
Warning
Non- Latching Cooling w/
Warning
Non- Latching All w/o
Warning
Non- Latching All w/o
Active
Modes
Criteria
[Inactive
Modes]
The current value for the cumulative compressor starts
and or hours for the given compressor have been
modified by a write override from TU.
Compressor involute pressure differential exceeded
Energized
allowable limits.
Ckt
Compressor involute pressure differential exceeded
Energized
allowable limits.
The unit is in active economizer cooling. The economizer
Economizer
(OAD) command has been greater than the economizer
Enabled
position by 10% for 5 continuous minutes.
The unit is in active economizer cooling. The economizer
Economizer
(OAD) command has been lower than the economizer
Enabled
position by 10% for 5 continuous minutes.
The unit is in any mode that is not active economizer
'Cooling w/
cooling. The OAD position has been lower than the
Economizer
minimum ventilation command by 10% for 5 continuous
Enabled'
minutes.
The unit is in any mode that is not active economizer
'Cooling w/
cooling. The OAD position has been greater than the
Economizer
minimum ventilation command by 10% for 5 continuous
Enabled'
minutes.
Troubleshooting
Reset
Level
Remote
Remote
Remote
Remote
Remote
Remote
Remote
67