Trane IntelliPak Programming Manual page 70

With symbio 800, 20 to 75 ton with the tracer td7 display
Table of Contents

Advertisement

Troubleshooting
Diagnostic Name
Affects
and Source
Target
Outdoor Air
Unit
Humidity Sensor
Active
Outdoor Air
Humidity Sensor
Active
OA Humidity
Sensor Active
Space Humidity
Unit
Sensor
Space Humidity
Sensor
Space Humidity
Sensor
Space Humidity
Unit
Sensor Active
Space Humidity
Sensor Active
Space Humidity
Sensor Active
Outdoor Airflow
Unit
Pressure Sensor
Outdoor Airflow
Pressure Sensor
Outdoor Airflow
Press Sensor
Space CO2
Unit
Sensor
Space CO2
Sensor
Space CO2
Sensor
Loss of Charge
Circuit
Lockout Cktx
Loss of Charge
Lockout Cktx
Loss of Charge
Lockout Cktx
Loss of Charge
Circuit
Detected Cktx
Loss of Charge
Detected Cktx
Loss of Charge
Detected Cktx
Space Pressure
Unit
Sensor
Space Pressure
Sensor
Space Press
Sensor
Airflow Assembly
Unit
Failure
Airflow Assembly
Failure
Airflow Assembly
Failure
70
Severity
Persistence
Warning
Non-Latching All
with
Special
Action
Warning
Non-Latching All
Warning
Non-Latching All
with
Special
Action
Warning
Latching
Warning
Non-Latching All
Immediate
Latching
Shutdown
Warning
Latching
Warning
Latching
w/ Special
Action
Warning
Latching
Active
Modes
Criteria
[Inactive
Modes]
The Active Outdoor Air Humidity sensor has failed out of
range.
This drives a 'fall back' response to Dry Bulb Economizer
and Energy Wheel decisions.
The Space Humidity sensor has failed out of range.
No action is taken for this sensor failure only the Outdoor
Air Humidity Sensor Active has special action.
The Space Humidity sensor value not available.
Dehumidification and humidification will be disabled.
Enthalpy based economizer decision will effectively be
disabled,
All
Outdoor Airflow pressure sensor has failed out of range Remote
Space CO2 sensor has failed out of range
All
Loss of Charge is detected on the circuit, severe enough
to shut down the circuit.
All
Loss of Charge is detected on the circuit, severe enough
to warn a technician, but not severe enough to shut down
the circuit.
All
Space Pressure sensor has failed out of range.
Statitrac control will be terminated and the Relief Fan
Speed and Relief Damper command will fall back to OA
Damper Tracking.
All
If the OA Damper > 50% and the Measured Airflow <=
Design Air Flow * .02 & >= -Design AirFlow * .02 for 10
consecutive seconds a latching, remote resettable,
'Airflow_Assembly_Failure' diagnostic will be generated.
Reset
Level
Remote
Remote
Remote
Local
Local
Remote
RT-SVP011A-EN