Trane IntelliPak Programming Manual page 68

With symbio 800, 20 to 75 ton with the tracer td7 display
Table of Contents

Advertisement

Troubleshooting
Diagnostic Name
Affects
and Source
Target
Relief Air Damper
Unit
Failed Closed
Relief Air Damper
Failed Closed
Rlf ir Damper Fail
Closed
Relief Air Damper
Unit
Failed Open
Relief Air Damper
Failed Open
Rlf Air Damper
Fail Open
OA Bypass
Unit
Damper Failed
Closed
OA Bypass
Damper Failed
Closed
OA Bypass Dmp
Fail Closed
OA Bypass
Unit
Damper Failed
Open
OA Bypass
Damper Failed
Open
OA Bypass Dmp
Fail Open
RA Bypass
Unit
Damper Failed
Closed
RA Bypass
Damper Failed
Closed
RA Bypass Dmp
Fail Closed
RA Bypass
Unit
Damper Failed
Open
RA Bypass
Damper Failed
Open
RA Bypass Dmp
Fail Open
Hydronic Heat
Unit
Actuator Failed
Closed
Hydronic Heat
Actuator Failed
Closed
HH Actuator Fail
Closed
68
Severity
Persistence
Warning
Non- Latching All
Warning
Non- Latching All
Warning
Non- Latching All
Warning
Non- Latching All
Warning
Non- Latching All
Warning
Non- Latching All
Warning
Non- Latching All
Active
Modes
Criteria
[Inactive
Modes]
The relief air damper position has been lower than the
damper command by 10% for 5 continuous minutes.
The relief air damper position has been greater than the
damper command by 10% for 5 continuous minutes.
The outdoor air bypass damper position has been lower
than the damper command by 10% for 5 continuous
minutes.
The outdoor air bypass damper position has been greater
than the damper command by 10% for 5 continuous
minutes.
The return air bypass damper position has been lower
than the damper command by 10% for 5 continuous
minutes.
The return air bypass damper position has been greater
than the damper command by 10% for 5 continuous
minutes.
The hydronic heat actuator position has been lower than
the actuator command by 10% for 5 continuous minutes.
Reset
Level
Remote
Remote
Remote
Remote
Remote
Remote
Remote
RT-SVP011A-EN