Trane IntelliPak Programming Manual page 60

With symbio 800, 20 to 75 ton with the tracer td7 display
Table of Contents

Advertisement

Troubleshooting
Diagnostic Name
Affects
and Source
Target
Unexpected
Circuit
Compressor
Shutdown
Cprsrxy
Unexpected
Compressor
Shutdown
Cprsrxy
Unexpected
Cprsr Shutdown
Compressor
Circuit
Failed to Start
Cprsrxy
Compressor
Failed to Start
Cprsrxy
Compressor
Failed to Start
Compressor
Circuit
Contactor Failure
Cprsrxy
Compressor
Contactor Failure
Cprsrxy
Compressor
Contactor Fail
Emergency Stop
Unit
Emergency Stop
Emergency Stop
60
Severity
Persistence
Immediate
Latching
Shutdown
Normal
Latching
Shutdown
Immediate
Latching
Shutdown
Special Action
(see Note)
Immediate
Latching
Shutdown
Active
Modes
Criteria
[Inactive
Modes]
All
A non-command shutdown of the fixed speed compressor
occurred. The controller detected that the input was not
proven. This could be a result from the following: High
pressure cutout or any fault from the compressor
protection module.
All
The fixed speed compressor failed to start when
commanded. The controller detected that the input was
not proven. This is could be the result of a compressor
protection module fault.
All
The fixed speed compressor failed to prove off when
commanded to shut down or the compressor proving
input was proven when the compressor was not
commanded to run. If a compressor proving input is
reporting that the compressor is still running 6 seconds
after the Symbio800 has Commanded it Off; then, this
warning diagnostic shall be active and the circuit will be
shutdown. If the compressor proves, but the Symbio800
has not Commanded it On, then it is assumed that a
compressor has started un-commanded. When the
compressor proving input is proven for more than 6
seconds the diagnostic will be generated and the circuit
will be shutdown.
Note: Possible future enhancement not included in Release 1.
If implemented the severity will have to go to Warning.
The following Special action will also be performed:
• The effected compressor will be continually
commanded off and a normal stop shall be commanded
to the Unit
• All other compressors on the effected circuit remain off
or will be shutdown
• If there is another circuit it will remain off or be will be
shutdown
• Heating will not be allowed to run
• The controller shall continue to run Head Pressure and
Superheat control and the supply fan shall continue to
run
All
Emergency stop feedback input has Opened. Time to trip
from input opening to unit stop shall be 0.1 to 1.0
seconds.
Reset
Level
Local
Local
Local
Local