Trane IntelliPak Programming Manual page 66

With symbio 800, 20 to 75 ton with the tracer td7 display
Table of Contents

Advertisement

Troubleshooting
Diagnostic Name
Affects
and Source
Target
Suction
Circuit
Temperature 2
Cktx
Suction
Temperature 2
Cktx
Suction Temp
Sensor
Suction Pressure
Circuit
Sensor Cktx
Suction Pressure
Sensor Cktx
Suction Press
Sensor
Discharge
Circuit
Pressure Sensor
Cktx
Discharge
Pressure Sensor
Cktx
Discharge Press
Sensor
Mixed Air
DX
Temperature
Cooling
Sensor Evapy
Mixed Air
Temperature
Sensor Evapy
Mixed Air Temp
Sensor
Evap Leaving Air
Unit
Coil Temp X
Sensor
Evap Leaving Air
Coil Temp X
Sensor
Evap Lvg Air
Temp Sensor
Outdoor Air
DX
Temperature
Cooling
Sensor
Outdoor Air
Temperature
Sensor
Outdoor Air
Temp Sensor
MP: Invalid
N/A
Configuration
MP: Invalid
Configuration
MP: Invalid
Configuration
66
Severity
Persistence
Immediate
Latching
Shutdown
Immediate
Latching
Shutdown
Immediate
Latching
Shutdown
Normal
Latching
Shutdown
Warning with
Latching
Special Action
Warning
Non-Latching All
N/A
Latching
Active
Modes
Criteria
[Inactive
Modes]
All
The suction temperature sensor has failed out of range. Remote
All
The suction pressure sensor has failed out of range.
All
The discharge pressure sensor has failed out of range.
All
Temperature sensor has failed out of range.
All
Temperature sensor has failed out of range.
The DX cooling continues to run but reheat for
dehumidification is stopped.
Temperature sensor has failed out of range.
All
MP has an invalid configuration based on the current
software installed.
Reset
Level
Remote
Remote
Remote
Remote
Remote
Remote
RT-SVP011A-EN