Trane IntelliPak Programming Manual page 65

With symbio 800, 20 to 75 ton with the tracer td7 display
Table of Contents

Advertisement

Diagnostic Name
Affects
and Source
Target
Supply Fan 1
Unit
Proving Failure
Supply Fan 1
Proving Failure
Supply Fan 1
Proving
Supply Fan 2
Unit
Proving Failure
Supply Fan 2
Proving Failure
Supply Fan 2
Proving
Relief Fan x
Unit
Proving Failure
Relief Fan x
Proving Failure
Relief Fan x
Proving
Space Pressure
Unit
Low
Space Pressure
Low
Space Pressure
Low
Space Pressure
Unit
Low
Space Pressure
Low
Space Pressure
Low
Suction
Circuit
Temperature 1
Cktx
Suction
Temperature 1
Cktx
Suction Temp
Sensor
RT-SVP011A-EN
Severity
Persistence
Warning with
Latching
Special Action
Warning with
Latching
Special Action
Warning with
Non-Latching All
Special Action
Warning
Non-Latching All
with Special
Action
Warning
Non-Latching All
with Special
Action
Immediate
Latching
Shutdown
Active
Modes
Criteria
[Inactive
Modes]
All
Any time the Supply Fan is expected to be running in Non
Bypass Mode, this diagnostic will be generated when a No
Flow condition exists for 40 continuous seconds.
Failure with Supply Fan 2 available:
Generate Supply Fan 1 Proving Failure
Diagnostic and Lockout all heating operation.
Failure with Supply Fan 2 NOT available:
Generate Supply Fan 1 Proving Failure
Shutdown the unit
All
Any time the Supply Fan 2 is expected to be running in
Non Bypass Mode, this diagnostic will be generated when
a No Flow condition exists for 40 continuous seconds.
Failure with Supply Fan 2 available:
Generate Supply Fan 1 Proving Failure
Diagnostic and Lockout all heating operation.
Failure with Supply Fan 2 NOT available:
Generate Supply Fan 1 Proving Failure
Shutdown the unit
Relief Fan x is expected to be running, this diagnostic will
be generated when a No Flow condition exists for 40
continuous seconds.
Failure w/ other relief fans available:
Generate RF x diagnostic. Take no other action.
Failure w/ no other relief fans available:
The relief damper will be closed, the relief fan will be
commanded off, economizing will be disabled and the
outside air damper will be driven to the active minimum
position.
The space pressure was low
Incomplete: Will re-visit when doing Return Fan
The space pressure was low
Incomplete: Will re-visit when doing Return Fan
All
The suction temperature sensor has failed out of range. Remote
Troubleshooting
Reset
Level
Remote
Remote
Remote
Remote
Remote
65