Trane IntelliPak Programming Manual page 63

With symbio 800, 20 to 75 ton with the tracer td7 display
Table of Contents

Advertisement

Diagnostic Name
Affects
and Source
Target
Emergency
Unit
Override Mode
Pressurize
Emergency
Override Mode
Pressurize
Emergency
Override Mode
Pressurize
Emergency
Unit
Override Mode
Depressurize
Emergency
Override Mode
Depressurize
Emergency
Override Mode
Depressurize
Emergency
Unit
Override Mode
Purge
Emergency
Override Mode
Purge
Emergency
Override Mode
Purge
Emergency
Unit
Override Mode
Shutdown
Emergency
Override Mode
Shutdown
Emergency
Override Mode
Shutdown
Emergency
Unit
Override Mode
Fire
Emergency
Override Mode
Fire
Emergency
Override Mode
Fire
Supply Fan
Unit
Bypass Enabled
Supply Fan
Bypass Enabled
Supply Fan
Bypass Enabled
Supply Fan
Unit
Bypass Proving
Failure
Supply Fan
Bypass Proving
Failure
Supply Fan
Bypass Proving
RT-SVP011A-EN
Severity
Persistence
Warning
Non-Latching All
Warning
Non-Latching All
Warning
Non-Latching All
Warning
Non-Latching All
Warning
Non-Latching All
Warning
Non-Latching All
Immediate
Latching
Shutdown
Active
Modes
Criteria
[Inactive
Modes]
The unit is following Emergency Override Pressurize.
The unit is following Emergency Override Depressurize. Local
The unit is following Emergency Override Purge.
The unit is following Emergency Override Shutdown.
The unit is following Emergency Override Fire.
This diagnostic is generated to notify BAS integrators as
to the presence of Supply Fan VFD Bypass mode.
All
Any time the Supply Fan is expected to be running in
Bypass Mode, this diagnostic will be generated when a No
Flow condition exists for 40 continuous seconds.
Troubleshooting
Reset
Level
Local
Local
Local
Local
Local
Remote
63