Interlock Switches
(Sectional)
1) Optional external interlock switches are
required with some Sectional or Rolling Steel
Doors to prevent the door from operating
under certain conditions including
the following:
•
If the door is equipped with a
functioning door lock, an interlock
switch (A) must be installed to prevent
electric operation when the lock
is engaged.
•
If the door is equipped with a pedestrian
pass-through door, an interlock switch (B)
must be installed at the pass-through
door in order to prevent electrical
operation when the pass-through door
is open.
2)
The switches must be set in the field.
NOTE: If External Interlock is used, THE JUMPER WIRE BETWEEN THE
EXT INTLK TERMINALS MUST BE REMOVED.
Pass door interlock:
Figure 6B
www.geniecompany.com
B
Should be open when
door is open.
Closed when door
is closed.
Side lock interlock:
Should be open when door
is locked. Closed when door
is unlocked.
CONTROL SIGNAL TERMINAL STRIP
SWITCH
075412-0000
(N.O.)
ANGLE
405964-0000
TRACK
A
STANDARD
SLIDELOCK
SWITCH
110324-0001
01-14
EXT
EXT
NTLK
NTLK
* REMOVE
*
JUMPER
WHEN
INSTALLING
EXTERNAL
INTERLOCK
(N.C.)
5.7