Interlock Switches - Genie GCL-MJ&MH Manual

Commercial/industrial door medium duty operator with tensibelt
Table of Contents

Advertisement

Interlock Switches

1) Optional external interlock switches are required with some
Sectional or Rolling Steel Doors to prevent the door from
operating under certain conditions including the following:
If the door is equipped with a functioning door lock, an
interlock switch must be installed to prevent electric
operation when the lock is engaged.
If the door is equipped with a pedestrian pass-through door,
an interlock switch must be installed at the pass-through
door in order to prevent electrical operation when the
pass-through door is open.
Pass door interlock:
Should be open when
door is open.
Closed when door is
closed.
NOTE: If External Interlock is used, THE JUMPER WIRE BETWEEN THE
EXT INTLK TERMINALS MUST BE REMOVED.
Side lock interlock:
Should be open when door is locked.
Closed when door is unlocked.
GCL-MJ&MH
Medium Duty Operator
OPEN
SWITCH
(N.O.)
ANGLE
Switches must
be set in
the field.
Figure 7
www.geniecompany.com
CONTROL SIGNAL TERMINAL STRIP
ODC
ODC
CLOSE
STOP
GND
1 BTN
STB
STB
SAFETY
SWITCH
(N.C.)
TRACK
08-12
N O
N O
EXT
EXT
SAFETY
INTLK
INTLK
STANDARD
SLIDELOCK
5.5