Installation
6. Connect the input and ground wires to the input terminal
7. Connect the output and ground wires to the output terminal
Table 1. UPS Wiring Specifications
Wire
Wire
Terminal
Terminal
Function
Position
Input
p
1
2
3
Output
p
4
5
6
2
*Use 2.0 mm
(14 AWG) 75EC copper wire minimum.
8. Replace the terminal block cover.
9. If an emergency power-off (disconnect) switch is required by
34
block according to Figure 19 and Table 1.
block according to Figure 19 and Table 1.
INPUT
1
Figure 19. Terminal Block
UPS Wire Function
EUH Models
EH Models
L2
N
G
G
L1
L
L2
N
G
G
L1
L
local codes, see "Remote Emergency Power-Off" on page 36 to
install the REPO switch before powering on the UPS.
Powerware
9125 User's Guide (2500–3000 VA)
®
OUTPUT
2
3
4
5
6
Terminal Wire
Terminal Wire
Size Rating*
2
2
2 16
2–16 mm
35 in lb (4.38 Nm)
35 in lb (4.38 Nm)
(14–8 AWG)
(14–8 AWG)
2
2
2 16
2–16 mm
35 in lb (4.38 Nm)
(14–8 AWG)
(14–8 AWG)
:
Rev B www.powerware.com
Tightening
Tightening
Torque
(
)