Powerware 9125 User Manual page 70

2500-3000 va
Hide thumbs Also See for 9125:
Table of Contents

Advertisement

Specifications
Table 5. Power Connections
Model
Model
PW9125-2500U
PW9125 2500U
PW9125-3000U
PW9125-2500EU
PW9125-3000EU
PW9125-2500E
PW9125-2500E
Country-specific detachable power cord
Country-specific, detachable power cord
PW9125-3000E
PW9125-2500EUH
PW9125-3000EUH
PW9125-2500EH
PW9125-3000EH
Table 6. Environmental and Safety
120V/208V Models (U, EU, EUH)
Operating
Temperature
Storage Temperature
Transit Temperature
Relative Humidity
Operating Altitude
Transit Altitude
Audible Noise
Surge Suppression
IEEE C62.41 Category B (formerly IEEE 587)
Safety Conformance
CSA C22.2, No. 107.1, 107.2; NOM-019-SCFI
Agency Markings
EMC (Class A)
64
Input Connection
Input Connection
6-ft, 5-30P attached power cord
6 ft 5 30P attached power cord
16A, IEC 320-C20 input connector
Terminal block
0°C to 40°C (32°F to 104°F)
Optimal battery performance: 25°C (77°F)
0°C to 25°C (32°F to 77°F)
-25°C to 55°C (-13°F to 131°F)
5–95% noncondensing
Up to 3,000 meters above sea level
Up to 10,000 meters above sea level
Less than 45 dBA Normal mode, typical load
Less than 50 dBA Battery mode
UL 1778, UL 497A;
UL, cUL, NOM-NYCE
FCC Part 15, ICES-003
Powerware
9125 User's Guide (2500–3000 VA)
®
Output Connections
Load Segment 1
Load Segment 2
(2) 5 15R and (2) 5 20R
(2) 5-15R and (2) 5-20R
(1) 5-30R output cord
(1) 5 30R output cord
(4) 10A, IEC 320-C13
(1) 16A, IEC 320-C19
Terminal block
230V Models (E and EH)
IEC 61000-4-5
IEC 60950; EN 50091-1-1; NOM-019-SCFI
CE, TUV-GS
EN 50091-2, IEC 62040-2
:
Rev B www.powerware.com