Powerware 9125 User Manual page 55

2500-3000 va
Hide thumbs Also See for 9125:
Table of Contents

Advertisement

Table 2. Configuration Mode LEDs and Options
Bar Graph Indicators Option
120, 208, or 230V
Nominal Input Voltage
110, 220, or 230V
Nominal Input Voltage
127 or 240V Nominal
Input Voltage
Site Wiring Fault
Alarm
AC Input Failure Alarm
NOTE
220V for EU and EUH models and 208V for E and EH models are also available. Contact the help desk at one of the
telephone numbers on page 70 for assistance.
Powerware
9125 User's Guide (2500–3000 VA)
®
LED Status
Explanation
On (default)
Nominal input voltage is on according to the following
models:
: 120V for U models
: 208V for EU and EUH models
: 230V for E and EH models
All other nominal input voltages are disabled.
Flashing
120, 208, or 230V is disabled; one of the other input
voltage options is selected.
On
Selecting this option changes the nominal input voltage
to one of the following:
: 110V for U models
: 220V for E and EH models
: 230V for EU and EUH models
Flashing
110, 220, or 230V is disabled; one of the other input
(default)
voltage options is selected.
On
Selecting this option changes the nominal input voltage
to one of the following:
: 127V for U models
: 240V for EU, E, EUH, and EH models
Flashing
127 or 240V is disabled; one of the other input voltage
(default)
options is selected.
On (default)
Alarm sounds when the polarity of the outlet is
reversed or the ground connection is missing; have a
qualified electrician repair the outlet wiring.
Flashing*
Alarm DOES NOT sound when the polarity of the outlet
is reversed or the ground connection is missing.
*For 208V or 230V units, flashing is the default; contact
your service representative to activate this alarm.
On (default)
Alarm sounds when there is an AC input failure.
Flashing
Alarm DOES NOT sound when there is an AC input
failure.
: