Front Door Installation; Louver Installation; Test For Flue Spillage; Optional Wall Thermostat - Regency ULTIMATE U38E Owners & Installation Manual

Freestanding gas stove
Table of Contents

Advertisement

installation
Front Door
Installation
1) Open the two side panels.
2) Slide the door
onto the two hinge
pins making sure
the two pieces
are flush together.
See diagram 1.
3) Close the door.
The latch plate
must be cen-
tered around the
alignment pin.
See
diagram 2. If the latch
plate interferes with the
corner of the stove you
Diagram 1
may want to angle the
plate slightly so the door
closes easier.
4) The latches should already be at the proper
setting. If they are too hard or too easy to close,
you may want to adjust them by loosening the
latch catch. See diagram 3.
Diagram 2
5) Remove the blue plastic protective coating
from the glass.
6) Test the seal around the door by placing a piece
of paper between the unit and the door, close
the door and try to pull the paper out. If it slips
out easily, then the door is not properly sealed.
Tighten or loosen the latch. See diagram 3.
Diagram 3
Note:
The door latch may require adjust-
ment as the door gasket material
compresses after a few fires and after
glass replacement. Turn the latch catch
inward or outward to loosen or tighten.
|
26
Regency
U38E-11 ULTIMATE Freestanding Gas Stove
®
Louver
Installation
1) Attach the top & bottom louvers to the side stove
panel using 2 screws per side.
Test for Flue
Spillage
A "spillage" test must be made before the installed
unit is left with the customer. Follow the procedure
below:
1) Start all exhaust fans in the home and any
other gas appliances. Then close all doors and
windows.
2) Light the unit and set controls to maximum.
3) After five minutes, test that there is a "pull" on
the flue by placing a smoke match, cigarette
or similar device which gives off smoke, on the
edge of the draft hood. See diagrams.
The smoke should be drawn into the draft hood.
If the smoke is not drawn into the draft hood, turn
the unit off and check for the cause of lack of draft.
Note: If the flue is blocked or has a strong
reverse flow, the thermally actuated safety
switch mounted in the draft hood will automati-
cally shut off the gas supply within about 10
minutes. If the heater turns off because of this
during the spillage test, check for the cause of
the lack of draft.
The thermally activated safety switch must be
manually reset before first startup.