Gas Connection; System Data; Gas Pipe Pressure Testing; 885 S.i.t. Valve Description - Regency ULTIMATE U38E Owners & Installation Manual

Freestanding gas stove
Table of Contents

Advertisement

Gas Connection

The gas line can be rigid pipe, or to make installation
easier, use a listed flexible connector if allowed by
local codes. Copper may also be used if approved
by local codes.
The gas connection at the valve is 3/8" NPT. For
minimum and maximum supply pressure see the
System Data Table.

System Data

U38E-11 with 38,000 BTU
U38E-NG11: For 0 to 2000 feet altitude
U38E-LP11: For 0 to 4500 feet alttitude
Burner Inlet Orifice Sizes:
Natural Gas
Burner
#32
Max. Input
Natural Gas
38,000 Btu/h
Propane
34,000 Btu/h
Min. Input
Natural Gas
26,000 Btu/h
Propane
27,500 Btu/h
Supply Pressure
Natural Gas
min. 7" w.c.
Propane
min. 11" w.c.
Manifold Pressure
Natural Gas
3.5" w.c.
Propane
10" w.c.
Electrical: 115_60Hz.
Circulation: Variable speed fan, 125/75 CFM.
Log Set: Ceramic fiber, 7 per set.
System Data:
HIGH ELEVATION - U38E-NG11
For 2,000 - 4,500 feet altitude
Burner Inlet Orifice Sizes:
Natural Gas
Burner
Max. Input Rating 35,000 Btu/h
Min. Input Rating 24,000 Btu/h
System Data
U38E-11 Converted to 30,000 BTU
For 0 to 4500 feet altitude
Burner Inlet Orifice Sizes:
Burner
Max. Input
Natural Gas
Propane
Min. Input
Natural Gas
Propane
Supply Pressure
Propane
Natural Gas
#50
Propane
Manifold Pressure
Natural Gas
Propane
Electrical: 115_60Hz.
Circulation: Variable speed fan, 125/75 CFM.
Log Set: Ceramic fiber, 7 per set.

Gas Pipe Pressure Testing

The appliance must be isolated from the gas sup-
ply piping system by closing its individual manual
shut-off valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 1/2 psig. (3.45 kPa). Disconnect piping
from valve at pressures over 1/2 psig (14" w.c.).
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note:
To properly check gas pressure, both
inlet and manifold pressures should
#33
be checked using the valve pressure
ports on the valve.
1. Make sure the valve is in the "OFF" position.
2. Loosen the "IN" (# 7) and/or "OUT" (# 6) pres-
sure tap(s), turning counterclockwise with a
1/8" wide flat screwdriver.
3. Attach manometer to "IN" and/or "OUT" pres-
sure tap(s) using a 5/16" ID hose.
4. Light the pilot and turn the valve to "ON" posi-
tion.
Natural Gas
Propane
#37
#52
30,000 Btu/h
30,000 Btu/h
21,000 Btu/h
23,000 Btu/h
min. 7" w.c.
min. 11" w.c.
3.5" w.c.
10" w.c.
Regency
5. The pressure check should be carried out with
the unit burning and the setting should be within
the limits specified on the safety label.
6. When finished reading manometer, turn off the
gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" flat screwdriver.
Screw should be snug, but do not over tighten.

885 S.I.T. Valve Description

1) 6 Stage flame adjustment
2) Pilot adjustment
3) Outlet Pressure Tap
4) Inlet Pressure Tap
5) Pilot Outlet
6) Main Gas Outlet
7) Main Gas Inlet
4
3
2
1
5
6

On Demand Pilot Light

Important: This appliance has a timer built into
the pilot light.
The timer starts when the main burner has been
shut-off by use of a remote control,thermostat or
on/off switch. The timer is set for 7 days. If there
has not been a call for heat for this 7 day period,
the pilot is designed to extinguish.
See lighting instructions for lighting pilot.
U38E-11 ULTIMATE Freestanding Gas Stove
®
installation
7
|