Owners & ULTIMATE U39 Freestanding Gas Stove Installation Manual www.regency-fire.com MODELS: U39-NG10 Natural Gas U39-LP10 Propane WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death, or property damage. - Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Page 2
To the New Owner: Congratulations! You are the owner of a state-of-the-art ULTIMATE Direct Vent Gas Stove by FPI Fireplace Products International Ltd. The Regency Gas Series of hand crafted appliances has been designed to provide you with all the warmth and charm ®...
Gas Connection ............25 Main Assembly ............41 High Elevation .............25 Burner & Log Assembly ..........42 Conversion from NG to LP ..........26 Door Assembly ............43 Conversion to Lower BTU Rating ........27 Warranty ..............47 Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
Page 4
Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
Page 5
NOTE: Regency units are constantly label is located on the inside of the drop ® This is a copy of the label that accompanies down pedestal door. being improved. Check the label on the each ULTIMATE Direct Vent Freestanding unit and if there is a difference, the label Gas Stove.
Page 6
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipm ent, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation. Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
ANY SAFETY SCREEN, GUARD, OR CIALLY THE FIREPLACE GLASS, AND SHOULD STAY AWAY TO AVOID BURNS BARRIER REMOVED FOR SERVICING OR CLOTHING IGNITION. AN APPLIANCE MUST BE REPLACED PRIOR TO OPERATING THE APPLIANCE. Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
Consult the building authority having because the appliance's metal pedestal base jurisdiction to determine the need for a permit prior This Regency Mobile/Manufactured ® extends the full width and depth of the appliance.
Minimum ceiling height is 36" / 914 mm from top e. Safety Screen of unit. f. Louver Installation g. 1-AA battery into DC spark box 9. Final check. Refer to the "Final Check" section. Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
The location of the termination cap must conform as ensuring that there is adequate accessibility for to the requirements in the "Exterior Vent Terminal servicing and proper operation. Locations" section. 10 | Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
* Clearance in accordance with local installation codes and the requirements of the gas supplier 3 feet (91cm) within a height of 15 feet (4.5m) above the meter / regulator assembly 3 feet (91cm) above - if within 10 feet (3m) horizontally Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
SV4BF TM-4CS Trim Plate-Black 4DT-TP 4DFPB 4DcP SV4LA TM-4TP Regency Fireplace Products . 6988 Venture St. . Delta, BC . Canada . V4G 1H4 . 604-946-5155 . www.regency-fi re.com 12 | Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
Page 13
Never allow the vent to run downward - this could cause high temperatures and may present a possible fi re hazard. Regency Fireplace Products . 6988 Venture St. . Delta, BC . Canada . V4G 1H4 . 604-946-5155 . www.regency-fi re.com...
, Selkirk Direct-Temp. AstroCap is a proprietary trademark of FPI Fireplace Products ® International Ltd. Dura-Vent® and Direct Vent are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc. 14 | Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
Exercise extreme caution when using ladders or on roof tops. Be aware of electrical wiring locations in walls and ceilings. Vent Restrictor setting at Vent Restrictor setting at 30,000 Btu/h 38,000 Btu/h Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
Page 16
Please note min. 1 foot between 90 elbows is required. Lengths do not include elbow indicated Vent restrictor position A (fully open). Refer to the "Venting Arrangement" section. 16 | Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
Be sure to check vent vertical centerline of the starter collar termination area after snow falls, on the unit. Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
Page 18
3 screws (#8 x 1/2, stainless steel). sidings. 15. Attach the pipe section onto the starter 6. A bead of non-hardening mastic should be 18 | Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
Dura-Vent Horizontal Termination Kit Wall Thimble (required for combus- You will require the following components with Planning Your Dura-Vent tible walls) your new Regency Direct Vent Freestanding ® Installation Gas Stove. Please review your product to make Minimum components for a Dura-Vent Vertical sure you have everything you need.
Page 20
7" diameter hole is acceptable. Note: Riser Vent is only for use in above grade terminations. Diagram 3a Diagram 2 20 | Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
Page 21
10. paint and attach with screws provided. Apply decorative brass or chrome trim if desired. See diagram 7. Diagram 5 Diagram 7 Diagram 10 Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
Slope "X" the problem. 0/12-2/12 4" 7. Ensure vent is vertical and secure the base 2/12-7/12 5-1/2" 7/12-12/12 6-3/4" 12/12-24/12 7-1/2" Diagram 13 24/12+ 12-1/2" Diagram 12 22 | Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
3. Connect the end of the Direct Vent system within the chimney. flex pipe section to the underside of the Top Adaptor using 3 sheet metal screws. Diagram 2. Diagram 2 Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
Page 24
4. To determine the length of flex required, Connector and secure with masonry bolts. with an adjustable length. Diagram 10. If you have a framed wall in 24 | Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
11. Unscrew the pilot orifice with the allen side. (Left side shown). key and replace with the LPG pilot orifice in the kit. Installer Notice: These instructions must be left with the appliance. 26 | Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ® 01.07.15 919-504...
2 screws. 13. Check operation of flame control. Check for proper flame appearance and glow on logs. Position the Log Bracket Restrictor between the Rear Log Bracket and the burner. Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
NOT covered under warranty. Note: Aeration Adjustment should only be performed by an authorized Regency ® Installer at the time of installation or service. To adjust the aeration: use the allen key to turn the turning gear which will adjust the air shutter.
1) Carefully remove the logs from the box and unwrap them. The logs are fragile, handle with care - do not force into position. B)02-56 918-039b Page 1 of 2 01/13/15 Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
Page 30
B)02-56 and on top of the cutout on Log A)02-65. 10) Separate platinum embers and place around the lava rock on the burner. Avoid stacking platinum A)02-65 embers. D)02-46 B)02-56 C)02-44 Cutout 30 | Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ® Page 2 of 2 918-039b 01/13/15...
Page 31
fl ows smoothly from one end of burner to the other. If there is any fl ame hesitation, check that area for any blockage of the burner port. A)02-65 A)02-65 B)02-56 E)02-45 E)02-45 C)02-44 Notch Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ® 918-039b 01/13/15...
Caution: Ensure that the wires do Wiring errors can cause not touch any hot surfaces and are improper and dangerous operation. away from sharp edges. 32 | Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
Note: Preferable if the thermostat is installed and the other on the right hand side. (Left side on an interior wall. shown). Regency offers an optional programmable ® thermostat but any 250-750 millivolt rated non- anticipator type thermostat that is CSA, ULC or UL approved may be used.
7. The unit should never be turned off, and on again without a minimum of a 60 second wait. Diagram 1 34 | Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
Page 35
Mettre le bouton de commande de gaz en position OFF pour éteindre la veilleuse. Pour économiser le carburant, éteignez la veilleuse quand l’appareil reste longtemps inutilisé. DO NOT REMOVE THIS INSTRUCTION PLATE 919-456 Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
The glass using the remote control. may require cleaning. Blower: Adjusting Flame Height Regency gas appliances use high tech blowers ® DO NOT ATTEMPT TO CLEAN THE to push heated air farther into the room. It is not unusual for the fan to make a "whirring"...
S E RV I C I N G A N A P P L I A N C E and should only be refinished with heat resistant MUST BE REPLACED PRIOR TO paint (not with wall paint). Regency uses ®...
5 mm Neoceram ceramic glass that will withstand the highest heat that your unit will produce. In the event that you break your glass by impact, purchase your replacement door from an authorized Regency dealer only, ® and follow our step-by-step instructions for Wraparound Assembly Door replacement.
5. Lift fan off of the 2 pins, tip back and pull through firebox opening. Disconnect the green ground wire from the right side of the fan as soon as you can reach it. Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
13. Remove the valve tray and replace. Stepper motor wire 6. If fan installed–disconnect the "Com" wire from the valve. 7. Disconnect the DC spark generator wires from the valve. 40 | Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
904-258 Side Panel Door Magnet *Not available as a replacement part. 948-255 Door Latch c/w Hook Flex Pipe 3" ID Hose Clamp 910-233 Thermodisc - Fan Auto/On/Off Mounting Bracket - Thermodisc Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
911-030 Fan Control Module 732-969 Conversion Kit LP 911-029 Valve/Remote Wiring Harness 911-093 120 Volt Power Cord (10 foot extension) 910-233 Fan Thermodisc *Not available as a replacement part. 42 | Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
Brushed Nickel Wrap Door - Complete 101. 846-570 Door Gasket Kit 105. Ceramic Paper 107. 936-243 Glass Gasket 111. Door Frame Fibre Paper 208. 940-325/P Wrap Glass *Not available as a replacement part. Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
Page 44
44 | Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
Page 45
Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
Page 46
46 | Regency U39-10 ULTIMATE Direct Vent Freestanding Gas Stove ®...
It is the general practice of FPI to charge for larger, higher priced replacement parts and issue credit once the replaced component has been returned to FPI and evalu- ated for manufacturer defect. The authorized selling dealer is responsible for all in-fi eld service work carried out on your Regency product. FPI will not be liable for results or costs of workmanship from unauthorized service persons or dealers.
Page 48
Register your Regency warranty online ® www.regency-fire.com Reasons to register your product online today! • View and modify a list of all your registered products. • Request automatic email notification of new product updates. • Stay informed about the current promotions, events, and special offers on related products.