Siemens SIPROTEC 5 Operation Manual page 59

V7.30 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Operator Element/Display Element
Besides the base module, you can fit an expansion module with key switches. The following table explains the
meanings of the switch positions.
Operator Element/Display Element
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-7, Edition 06.2016
5.2 Overview of Operator Elements and Display Elements
Meaning
8 parameterizable LEDs
Monochrome (red)
Keypad
Keypad with programmable function keys to perform
actions quickly. Next to the keypad there are labeling strips
for user-defined labels.
Meaning
Key switch for on-site switching authority
Local position
Switching commands for configured equipment are
possible only on site with the control keys or in the control
menu. You cannot execute switching commands remotely
(or from DIGSI).
Remote position
Switching commands for configured equipment are
possible on site as well as remotely.
In devices with an expansion module with key switches the
corresponding options are static in the control menu.
Key switch for on-site switching mode
OFF position
Unlocked switching of configured equipment allowed
Normal position
Switching of configured equipment only with the designed
interlocking conditions
In devices with an expansion module with key switches the
corresponding options are static in the control menu.
Using On-Site Operation Panel