Siemens SIPROTEC 5 Operation Manual page 193

V7.30 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

The following dialog allows you to select the devices to be updated and their firmware components.
[scfwupsd-090413-01.tif, 2, en_US]
Figure 9-7
At this point, the different versions are displayed to you.
Press the Update button.
²
Select the device or the communication module that must be updated.
²
In order to start the update, click Update device(s) in the top section.
²
After the data have been transferred successfully to the device, the firmware update starts automatically on
the SIPROTEC 5 device.
[scfwdvlo-220813-01, 1, en_US]
NOTE
i
i
The device does not perform any functions during the update.
In some cases, the update can take several minutes and may restart the device several times. Never switch
off the device during the update.
Following the firmware update of the device and the communication modules, all firmware components of
the device are updated:
You will find more information on this under
²
Special Features When Handling Protocols
The firmware of the communication modules consists of the base firmware and all available protocols. The
communication drivers depend on the device firmware and must be updated together with the firmware.
If a protocol is parameterized in DIGSI and the configuration is loaded into the device, the protocol firmware is
loaded automatically into the device, if necessary.
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-7, Edition 06.2016
Selecting Firmware Update
Maintenance, On-the-Spot Assistance and Test
9.4 Firmware and Parameter Set Update
Structure of the HW/SW Information Menu Item, Page
183.
193